| Plan Review Notes For Permit 04051040 |
| Permit Number |
04051040 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-11-05 00:00:00 | 1) ELEVATOR WARNING SIGNS REQUIRED | | | AT EACH ELEVATOR OPENING. | | | | | | 2) ALL VERTICAL SHAFTS ARE TO BE FIRE | | | SPRINKLER PROTECTED. | | | | | | 3) REQUIRED FIRE ALARM SYSTEM SHALL | | | BE UL LISTED FOR CENTRAL STATION | | | SERVICE. | | | | | | 4) SMOKE DETECTORS SHALL BE INSTALLED | | | A MINIMUM OF THREE FEET OF AIR | | | CONDITIONER DIFFUSERS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|