| 2004-11-01 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04051040 |
| | ADD: 2485 METROCENTRE BLVD |
| | CONT: PARAG CONSTRUCTION |
| | TEL: (754)264-6192 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | 3RDREVIEW |
| | ACTION: DENIED |
| | |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | THE NOC BY FL STATE LAW NEEDS TO BE |
| | RE-RECORDED, NO WORK HAS STARTED AFTER |
| | 90 DAYS OF RECORDING. |
| | |
| | 2) SOILS REPORTS: |
| | A) (3) ORIGINAL SIGNED & SEALD SOILS |
| | REPORTS ARE REQUIRED. |
| | B) (3) ORIGINAL DENSITY REPORTS BY |
| | NUTTING. |
| | PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 3) PROVIDE ENERGY CALS, (3) REQUEST, |
| | FL BLD CODE CHAP 13 ENERGY EFFICENCY |
| | PROVIDE ENERGY CALS/ W MANUAL "J" |
| | |
| | 4)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | COMMENT# 7 FROM PREVIOUS REVIEW, |
| | THE DO NOT MATCH, THE FLOOR PLAN VS THE |
| | ELEVATION, ON THE ELEVATION (NORTH) OF |
| | SHEET A-1 (2) WINDOWS ARE MISSING ON |
| | EACH FLOOR. SEE ROOMS 100,102,104,106 & |
| | 108. MISSING WINDOWS IN ROOMS 100 & |
| | 108. |
| | |
| | 5)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) EXTERIOR STEEL DOORS |
| | B) EXTEIOR GLAZED DOORS |
| | C) EXTERIOR AUTO FRONT ENTRY DOORS |
| | D) EFIS SYSTEMS |
| | E) WALL LOUVER |
| | F) STRUCTURAL COMPONENTS |
| | 1) WOOD CONNECTORS/ TRUSS CONNECTORS |
| | 2) EXTERIOR RAILINGS |
| | G) ROOF ASEMBLIES, FLAT, UNDERLAYMENT, |
| | ROOF TILES |
| | |
| | 6)THE STRUCTURAL AND ARCHITECTURAL |
| | PLANS |
| | DO NOT PROVIDE SUFFICENT INFORMATION ON |
| | THE PORT COCHERE CEILING.NOTE (11) FROM |
| | THE PREVIOUS REVIEW. |
| | A) PROVIDE THE ATTACHMENT INFORMATION |
| | BE |
| | TWEEN THE METAL HIGH-HAT AND BAR JOIST. |
| | B) PROVIDE MANUFACTURERS RECOMMENDATION |
| | (APPROVAL) FOR EXTERIOR CEILINGS OR |
| | SOFFITS. |
| | C) SHEET A-5 PORT COCHERE DETAIL |
| | DOESN'T |
| | INDICATE THE FINISH MATERIAL TO BE USED |
| | |
| | OVER THE GYPSUM SHEATHING, PLEASE GIVE |
| | FINISH. NOTE UNDER LIMITATIONS FOR |
| | EXTER |
| | IOR GYPSUM SHEATHING IS NOT A SUITABLE |
| | SUBTRATE FOR THE DIRECT APLICATION OF |
| | STUCCO, PAINT OR TEXTURES. |
| | |
| | 7) NOTE# 16 FROM THE PREVIOUS REVIEW, |
| | STORAGE ROOM NEXT TO THE STAIRWELL AT |
| | EACH END OF THE BUILDING DO NOT PROVIDE |
| | |
| | FIRE RATED DOORS, SEEA-6 DOOR SCHEDULE |
| | DOOR# 15. TABLE 704.1 OCCUPANCY SEPERA- |
| | TION S2 LOW HAZARD 2HR. |
| | |
| | 7B) NOTE# 16 FROM THE PREVIOUS REVIEW: |
| | PROVIDE THE EQUIVALANT THICKNESS FOR THE |
| | BLOCK WALL SEPERATING THE STORAGE ROOMS |
| | AND SUITES. EQUIVALANT THICKNESS IS TO |
| | BE PROVIDED BY THE BLOCK MANUFACTURER |
| | FOR A 2 HR WALL, SEE 709.3.1. |
| | |
| | 8) NOTE# 20 FROM PREVIOUS REVIEW: |
| | A) SHEET S-5 DETAIL "A" CORRECT SIZE OF |
| | |
| | BOLTS TO BE USED IN FOOTER 4-34/DIA. |
| | B) COLUMN SPLICE WHAT TYPE OF METALS |
| | ARE |
| | TO BE USED FOR THE "SPLICE" WHAT TYPE OF |
| | |
| | WELD & THICKNESS. |
| | C) STEEL COLUMN INDICATES THE USE OF A |
| | 4"X4", BUT NO THICKNESS IS PROVIDED? |
| | D) SAME DETAIL CAP PLATES INDICATE SEE |
| | COLUMN SCHEDULEFOR THE SIZE BUT WHERE? |
| | PROVIDE THE SIZE, THICKNESS AND THE |
| | WELD |
| | AND THE AMOUNT OF WEIGHT TO BE |
| | RESISTED. |
| | ARE GUSSET PLATES REQUIRED FOR UNDER THE |
| | |
| | CAP PLATES? |
| | |
| | 9) MISSING THE ROOF FRAMING IN REGAURDS |
| | |
| | TO THE CONCRETE ROOF DECK. |
| | |
| | 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |