Text |
| 2004-08-09 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: |
| | 5) ALL ARCHITECTURAL SHEETS SHALL SHOW |
| | THE PRINTED NAME OF THE PERSON RESPONSI- |
| | BLE FOR SEALING THE DOCUMENT. FAC 61G1- |
| | 16.004(6) & FS 481.2055. - SHEETS A-1.1C |
| | AND A-3.1A PRINTED NAME MISSING. |
| | FROM PREVIOUS REVIEW: |
| | 6) SHT A-4.1 ROLL IN SHOWER DETAIL, SHOW |
| | DETAIL FOR SEAT 11-4.21.3, GRAB BARS 11- |
| | 4.21.4, CONTROLS 11-4.21.5, & SHOWER |
| | UNIT 11-4.21.6. - ALSO SEE FIGURES 37B, |
| | 57A AND 57B. |
| | FROM PREVIOUS REVIEW: |
| | 22) SHTS P-2.5 & P-2.6 MANY RISERS DO |
| | NOT REFLECT THE FLOOR PLANS. CORRELATE |
| | THE RISERS AND FLOOR PLANS. SEC 104.2.1. |
| | D) 1 WATER CLOSET ON FLOOR PLAN BUT 2 |
| | SHOWN ON RISER. |
| | H) P2.4 STATES 2ND FLOOR ONLY, BUT RIS- |
| | ER AND FLOOR PLAN SHOWS 2ND AND THIRD |
| | FLOOR. |
| | M) FLOOR DRAIN NOT VENTED. SEC 901.2.1 |
| | AND 907.1 - NO OFFSETS ALLOWED ON WASTE |
| | STACK SECTION 910.2 |
| | Q) WASH MACHINE REQUIRES A STANDPIPE |
| | SECTIONS 1002.1 & 802.4, AND A CLEANOUT |
| | 4' ABOVE THE FLOOR SECTION 708.10. |
| | Z) FLOOR DRAIN IS NOT VENTED. SECTIONS |
| | 901.2.1 & 907.1 |
| | FROM PREVIOUS REVIEW: |
| | 31) FOLLOWING INFORMATION REQUIRED FOR |
| | GAS APPROVAL/PERMIT. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. - NOT ALL PIPE SIZE AND |
| | LENGTHS OF PIPE ARE SHOWN. MINIMUM 1-1/2 |
| | INCH PIPE REQUIRED FROM THE METER TO THE |
| | 1-1/4X1-1/4X1-1/2 INCH TEE. MIN. 1-1/4" |
| | REQUIRED TO THE FIRST HEATER WITH 1" RE- |
| | QUIRED TO THE OTHER 2 HEATERS ON 1/2 LB |
| | SYSTEM MAXIMUM 20'. (THIS DISTANCE IS |
| | NOT SHOWN ON RISER DIAGRAM). DOES EACH |
| | DRYER AND SINGLE WATER HEATER HAVE A 2 |
| | LB. TO 1/2 LB. REGULATOR? INDICATE ON |
| | RISER DIAGRAM. SHOW ALL LENGTHS OF PIPE |
| | AND PIPE SIZES. INDICATE WHERE PRESSURE |
| | CHANGES. |
| | NEW COMMENT: |
| | 1B) SEE ATTACHED SHEET CONCERNING FS |
| | 553.80(2)(B) DESIGN PROFESSIONAL DOCU- |
| | MENTS. |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |