| 2004-06-17 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SHT SP-1 RPZ BACKFLOW IS REQUIRED ON |
| | THE WATER SERVICE. PLAN SHOWS A BACKWAT- |
| | ER VALVE. SECTIONS 608.13.2 & 104.2.1. |
| | 2) SHT SP-1 MORE INFORMATION REQUIRED ON |
| | THE ENTRANCE FOUNTAIN. WILL THERE BE A |
| | DRAIN AND OR WATER SUPPLY TO THE FOUNT- |
| | AIN? IF SO SHOW PIPING AND TERMINATION |
| | OF DRAIN AND THE WATER SUPPLY SHALL BE |
| | EQUIPPED WITH AN RPZ BACKFLOW. SECTION |
| | 104.2.1. |
| | 3) SHT A-1.1 THE FOLLOWING TOILET ROOMS |
| | SHALL BE ACCESSIBLE AND SHALL CONFORM TO |
| | SECTION 11-4.22. THE WORKSHOP/MAINT., |
| | TOILET ROOMS AT LANUDRY ROOM, MENS AND |
| | WOMENS TOILET ROOMS NEAR THE EXERCISE |
| | ROOM. SUBMIT A DETAIL SHOWING COMPLIANCE |
| | WITH SECTIONS 11-4.16, 11-4.19, AND |
| | 11-4.22 AND ALL SUBSECTIONS. |
| | 4) SHT A-1.1 SINKS IN EMPLOYEE AREA ARE |
| | TO BE ACCESSIBLE. SUBMIT A DETAIL TO |
| | SHOW COMPLIANCE WITH 11-4.24 AND ALL |
| | SUBSECTIONS. |
| | 5) ALL ARCHITECTURAL SHEETS SHALL SHOW |
| | THE PRINTED NAME OF THE PERSON RESPONSI- |
| | BLE FOR SEALING THE DOCUMENT. FAC |
| | 61G1-16.004(6) & FS 481.2055. |
| | 6) SHT A-4.1 ROLL IN SHOWER DETAIL SHOW |
| | DETAIL FOR SEAT 11-4.21.3, GRAB BARS 11- |
| | 4.21.4, CONTROLS 11-4.21.5, SHOWER UNIT |
| | 11-4.21.6. |
| | 7) SHT A-4.2 SHOW A DETAIL FOR THE KING |
| | JAC SUITE THAT IS TO BE ACCESSIBLE. |
| | SECTION 104.2.1. |
| | 8) SHT A-4.2 HDCP DETAILS, WATER CLOSET |
| | SHALL NOT BE IN THE TURNING AREA. THE |
| | AREA SHALL BE UNOBSTRUCTED PER SECTIONS |
| | 11-4.2.3 & 11-4.22.3. |
| | 9) SHT A-5 ROOF PLAN, SHOW GUTTER SIZE |
| | FOR LOWER FLAT ROOF. SHOW LOCATION OF |
| | DOWNSPOUTS. PLAN INDICATES THAT THE GUT- |
| | TER IS ON ALL SIDES OF ROOF. SHOW SQUARE |
| | FOOTAGE OF ROOF AND SHOW 1/2 AREA OF ALL |
| | VERTICAL WALLS ADDED TO AREA OF ROOF FOR |
| | SIZING GUTTERS AND DOWNSPOUTS PER SECT- |
| | IONS 1106 & 1107 AND ALL SUBSECTIONS. |
| | 10) ROOF PLAN, ONE AREA SHOWS 1554 SF & |
| | WALL AREA 6450 SF FOR A TOTAL OF 8004 SF |
| | THIS AREA WILL REQUIRE TWO 4" ROOF |
| | DRAINS. TWO 3" DRAINS ARE SHOWN. TABLE |
| | 1106.2 - THE SCUPPER SHOWN IN THIS ARE |
| | IS NOT SIZED FOR THIS AREA. SCUPPER SIZE |
| | SHALL MINIMUM 85 SQ. IN. SECTION 1107.3 |
| | - THE AREA WITH FOUR DRAIN WITH A SQUARE |
| | FOOTAGE OF 2580 SF AND WALL AREA OF 326 |
| | SF SHOWS NO SCUPPERS FOR THESE AREAS. - |
| | SECTION 1503.4.2 STATES "SCUPPER SHALL |
| | BE LOCATED AS CLOSE AS PRACTICAL TO REQ- |
| | UIRED VERTICAL LEADERS. THIS DOES NOT |
| | COMPLY WITH THE INTENT OF THE CODE. |
| | 11) SHT A-5 "SCUPPER SEE SHT A-6 DETAIL |
| | "A". NO DETAIL A ON SHT A-6, SCUPPER DE- |
| | TAIL IS #1. PLEASE CORRELATE PLANS. SEC- |
| | TION 104.2.1 |
| | 12) SHT A-6 DETAIL #1 SCUPPER INDICATE A |
| | 3"X15" SCUPPER, SECTION 1503.4.2 STATES |
| | THAT SCUPPERS SHALL BE A MINIMUM OF 4" |
| | IN HEIGHT. SUBMIT NEW SCUPPER DETAIL. |
| | SHOW TYPE OF MATERIAL USED FOR SCUPPERS. |
| | SECTION 104.2.1 |
| | 13) IN ADDITION TO THOSE ACCESSIBLE |
| | SLEEPING ROOMS AND SUITES REQUIRED BY |
| | 11-9.1.2, SLEEPING ROOMS AND SUITES THAT |
| | COMPLY WITH 11-9.3 (VISUAL ALARMS, NOTI- |
| | FICATION DEVICES, AND TELEPHONES) SHALL |
| | BE PROVIDED. 3 UNITS ARE REQUIRED PER |
| | SECTION 11-9.1.3. PROVIDE INFORMATION |
| | SHOWING WHICH ROOMS ARE IN COMPLIANCE. |
| | 14) SHT A-14 DETAILS 1 & 3, SHOW DETAILS |
| | PER SECTIONS 11-4.16.2 CLEAR FLOOR SPACE |
| | 11-4.16.3 HEIGHT, 11-4.16.4 GRAB BARS, |
| | 11-4.16.5 FLUSH CONTROLS. |
| | 15) SHOW LOCATION FOR HDCP KING SUITE. |
| | NONE SHOWN ON FLOOR PLAN, BUT SHT A-1.2 |
| | INDICATES THERE IS ONE. SECTION 104.2.1 |
| | 16) ALL PLUMBING & MECHANICAL SHEETS, |
| | A PROFESSIONAL ENGINEER SHALL SIGN HIS |
| | NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| | SPECIFICATIONS, REPORTS AND FINAL BID |
| | DOCUMENTS PROVIDED TO THE OWNER OR THE |
| | OWNER'S REPRESENTATIVE, OR OTHER DOCU- |
| | MENTS PREPARED OR ISSUED BY SAID REGIS- |
| | TRANT AND BEING FILED FOR PUBLIC RECORD. |
| | THE DATE THAT THE SIGNATURE AND SEAL IS |
| | AFFIXED AS PROVIDED HEREIN SHALL BE EN- |
| | TERED ON SAID PLANS, SPECIFICATIONS, RE- |
| | PORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL |
| | ENGINEER, FAC 61G15-23.002(1) |
| | FS 471.025 |
| | EACH SHEET OF PLANS AND PRINTS WHICH |
| | MUST BE SEALED UNDER THE PROVISIONS OF |
| | CHAPTER 471 SHALL BE SEALED, SIGNED AND |
| | DATED BY THE PROFESSIONAL ENGINEER IN |
| | RESPONSIBLE CHARGE. FAC 61G15-23.002(2) |
| | FS 471.025 |
| | - THE SIGNATURES ON THESE SHEETS ARE |
| | COPIES, AND AS SUCH THEY ARE NOT APPROV- |
| | ED. A "WET SIGNATURE" IS REQUIRED ON THE |
| | SEAL OF EACH SHEET. |
| | 16) SHT P-2.1 A VENT IS REQUIRED FOR THE |
| | FLOOR DRAIN AND SPA DRAIN. SECTION 901.2 |
| | .1 |
| | 18) SHTS P-2.1 & P-2.2 SHOW NUMEROUS 2" |
| | ROOF DRAIN LINES. WHAT ARE THESE LINES |
| | DRAINING AND WHERE DO THEY TERMINATE. |
| | PLEASE CLARIFY. SECTION 104.2.1 |
| | 19) SHT P-2.1 NO SANITARY DRAIN LINE |
| | SHOWN FOR WATER CLOSET IN TOILET ROOM |
| | AT WORKSHOP/MAINT. SECTION 104.2.1 |
| | 20) SHTS P-2.5 & P-2.6 RISERS A, C, K, |
| | M, O, P, Q, & R FIXTURE SK-2 IS SHOWN AS |
| | AN "S" TRAP. THIS IS NOT APPROVED PER |
| | SECTION 1002.3. - THE SK-2 SINK SHALL |
| | NOT CONNECT BELOW THE SLAB AS SHOWN, BUT |
| | SHOULD CONNECT 18" TO 20" ABOVE THE SLAB |
| | SECTION 104.2.1 |
| | 21) SHTS P-2.5 & P-2.6 IDENTIFY ALL FIX- |
| | TURES ON THE RISERS. SECTION 104.2.1 |
| | 22) SHTS P-2.5 & P-2.6 MANY RISERS DO |
| | NOT REFLECT THE FLOOR PLANS. PLEASE |
| | CORRELATE THE RISERS AND FLOOR PLANS. |
| | SECTION 104.2.1. |
| | 23) SUBMIT WATER RISER ISOMETRICS FOR |
| | EACH UNIT. SHOW ALL PIPE SIZING AND SHOW |
| | WATER HAMMER ARRESTORS REQUIRED BY SECT- |
| | ION 604.9 AND LOCATED NEAR THE FIXTURE, |
| | NOT IN THE CEILING PER PDI-WH 201. |
| | SECTION 104.3.1.1. |
| | 24) SUBMIT A SANITARY BLDG DRAIN ISOMET- |
| | RIC SHOWING ALL PIPE SIZES AND DFU'S AS |
| | THEY ACCUMULATE IN THE SYSTEM. SECTION |
| | 104.3.1.1. |
| | 25) SUBMIT A STORM BLDG DRAIN ISOMETRIC |
| | SHOWING ALL PIPE SIZES AND SQUARE FOOT- |
| | AGE AS IT ACCUMULATES IN THE SYSTEM. |
| | SECTION 104.3.1.1. |
| | 26) SUBMIT STORM RISER DIAGRAMS SHOWING |
| | PIPE SIZES AND SQUARE FOOTAGE. SECTION |
| | 104.3.1.1 |
| | 27) INFORMATIONAL: A SEPARATE GAS PERMIT |
| | AND SEPARATE IRRIGATION PERMIT REQUIRED. |
| | 28) SHT G-1.1 GAS CONNECTION SCHEDULE |
| | INDICATES KITCHEN EQUIPMENT MAY BE IN- |
| | STALLED. THIS IS NOT SHOWN ON THE RISER |
| | DIAGRAM. PLEASE CLARIFY SECTION 104.2.1. |
| | 29) SUBMIT MANUF. SPECIFICATION SHEETS |
| | FOR THE REGULATORS. |
| | 30) SHT G-1.1 A SHUT OFF VALVE AND A |
| | UNION ARE REQUIRED UPSTREAM OF THE REGU- |
| | LATORS. |
| | 31) FOLLOWING INFORMATION REQUIRED FOR |
| | GAS APPROVAL/PERMIT. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. NO PIPING SHOWN TO METER. |
| | B. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). - PLANS SHOW |
| | 255' TO METER, BUT CUT SECTIONS OF PIPE |
| | ADD UP TO 190'. PLEASE SHOW ALL CUT SEC- |
| | TIONS OF PIPE SO THAT PLANS CORRELATE. |
| | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | |
| | REVIEW BY KEN STEVENS |