| Date |
Text |
| 2004-05-25 00:00:00 | 1) ALL DEMOLITION, RENOVATION, AND |
| | CONSTRUCTION TO COMPLY WITH NFPA 241. |
| | |
| | 2) SUITABLE ROADS ARE REQUIRED DURING |
| | CONSTRUCTION FOR FIRE AND PARAMEDICAL |
| | ACCESS. |
| | |
| | 3) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| | TO, DURING AND AFTER CONSTRUCTION. |
| | |
| | 4) BUILDING ADDRESS NOT SHOWN ON |
| | ELEVATION DRAWING. A MINIMUM OF AT LEAST |
| | 6" HIGH NUMBERS ARE REQUIRED. |
| | |
| | 5) A KNOX-BOX WILL BE REQUIRED. |
| | |
| | 6) KNOX-BOX LOCKING CAPS WILL BE |
| | REQUIRED FOR THE FIRE DEPARTMENT |
| | CONNECTION. |
| | |
| | 7) PLEASE PROVIDE PRODUCT APPROVALS |
| | FOR FIRE RATED GLAZING SHOWN ON |
| | PAGE A-1.1A. |
| | |
| | 8) PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATIONS FOR WALLS AND CEILINGS. |
| | |
| | 9) TACTILE SIGNAGE REQUIRED AT EXITS. |
| | |
| | 10) ALL SHAFTS THAT ARE LARGE ENOUGH |
| | FOR PERSONS TO FALL INTO MUST BE |
| | MARKED SHAFTWAY WITH 6" HIGH LETTERS. |
| | |
| | 11) OCCUPANT EMERGENCY INSTRUCTIONS |
| | SHALL BE POSTED. PLEASE INDICATE |
| | LOCATIONS. |
| | |
| | 12) PLEASE INDICATE PRESCRIPTIVE |
| | STRENGTH REQUIREMENTS FOR ALL HANDRAILS |
| | AND GUARDRAILS. |
| | |
| | 13) HOW DO THE SINGLE SMOKE DETECTOR |
| | IN ROOMS MEET THE CURRENT REQUIREMENTS. |
| | |
| | 14) ELECTRONIC SWITCHES, CHAIN AND |
| | LOCK REQUIRED ON FIRE LINE BACKFLOW |
| | DEVICE. |
| | |
| | 15) NO FIRE SPRINKLER PLANS PROVIDED. |
| | |
| | 16) PLEASE DISPLAY ALL FIRE EXTINGUISHER |
| | LOCATIONS. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |