| Plan Review Notes For Permit 04051036 |
| Permit Number |
04051036 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-07-29 00:00:00 | 1) ATRIUM WORDING STILL REMAINS ON | | | CERTAIN PAGES OF THE PLAN. IF IT IS | | | NOT AN ATRIUM, THEN REMOVE ALL | | | REFERENCES. | | | | | | 2) THE OTHER MAJOR PROBLEM THAT | | | STILL SEEMS CONFUSING IS WHEN THE | | | PARTITIONS AND DOORS ARE REMOVED THEN | | | BOTH STAIRS WILL COMMNUNICATE WITH | | | ALL PORTIONS OF THE BUILDING. IT IS | | | KNOWN THAT THE STAIRS ARE NOT RATED | | | BUT EXITS ARE DEFINED AS "THAT PORTION | | | OF THE MEANS OF EGRESS THAT IS SEPARATED | | | FROM ALL OTHER SPACES OF A BUILDING | | | OR STRUCTURE BY CONSTRUCTION OR | | | EQUIPMENT AS REQUIRED TO PROVIDE A | | | PROTECTED WAY OF TRAVEL TO THE EXIT | | | DISCHARGE". RE: NFPA 101, THE LIFE | | | SAFETY CODE, DEFINITIONS. PLEASE | | | ADVISE. | | | | | | THE REVISED PLANS ARE MUCH CLEARER | | | AND SEEM TO ILLUSTRATE THE PROPOSED | | | WORK MUCH BETTER. THANK YOU. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|