| 2004-05-26 00:00:00 | 1) PLEASE EXPLAIN EXITING FROM THE |
| | FIRST FLOOR PARKING AREA WITH THE |
| | PROPOSED ADDITION OF THE TWO NEW |
| | SIX FOOT HIGH SITE WALLS. |
| | |
| | 2) WHAT FIRE PROTECTION FEATURES ARE |
| | PLANNED FOR THE NEW PROPOSED ATRIUM. |
| | PLEASE SEE NFPA 101, THE LIFE SAFETY |
| | CODE, 2000 EDITION, SECTION 8-2.5.6 |
| | FOR REQUIREMENTS AND EXCEPTIONS THAT |
| | NEED TO BE UNDERSTOOD AND DEMONSTRATED. |
| | |
| | 3) THE NEW STOREFRONT GLAZING ADJACENT |
| | TO EXISTING PARKING WILL PROVIDE |
| | WHAT SEPARATION. |
| | |
| | 4) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENTS FOR NEW HANDRAILS AND OR |
| | GUARDRAILS. |
| | |
| | 5) PLEASE EXPLAIN FULL WIDTH ROLL |
| | DOWN DOOR AND HOW WILL IT AFFECT |
| | INGRESS AND EGRESS. |
| | |
| | 6) PLEASE EXPLAIN FIRE RATING ON |
| | BUILDING SECTION |
| | |
| | 7) DEBRIS SHALL BE REMOVED DAILY FROM |
| | THE SITE. |
| | |
| | 8) BUILDING ADDRESS NOT SHOWN ON |
| | ELEVATION DRAWING. |
| | |
| | 9) PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILINGS. |
| | |
| | 10) PLEASE SHOW ALL FIRE RATINGS AND |
| | FIRE PROTECTION. |
| | |
| | 11) PLEASE DEMONSTRATE COMPLIANCE WITH |
| | FBC 414, 414.4, AND 414.5. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |