Plan Review Notes
Plan Review Notes For Permit 04051005
Permit Number 04051005
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ARCHITECTURAL SHEETS, TITLE BLOCK RE-
 QUIRES FIRM LICENSE NUMBER, DATE PREPAR-
 ED, PRINTED NAME OF PERSON SEALING DOCU-
 MENT, AND CERTIFICATE OF AUTHORIZATION
 NUMBER. FAC 61G1-16.004 & FS 481.219
 2) SINKS SHALL COMPLY WITH SECTION 11-4.
 24 AND ALL SUBSECTIONS. SUBMIT A DETAIL
 KNEE CLEARANCE 11-4.24.3, DEPTH 11-4.24.
 4, EXPOSED PIPES AND SURFACES 11-4.24.6,
 3) SHT A231 ROOMS 931, 937, AND 961,
 SHOW CLEAR FLOOR SPACE 11-4.24.4 AND A
 TURNING AREA 11-4.2.3 ON FURNITURE PLAN
 TO SHOW HOW FURNITURE IMPACTS THE CLEAR
 FLOOR SPACE AND THE TURNING AREA.
 4) SHT P3 PLUMBING SPECIFICATIONS: 7 & 8
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM REFERENCES.
 5) SHT P3 WATER RISER DIAGRAMS. SHOW THE
 LOCATION FOR THE WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9. (AT ICE
 MAKERS). SHOW LOCATION AT FIXTURE NOT IN
 THE CEILING. PDI-WH 201 & MANUF. INSTALL
 INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]