| Plan Review Notes For Permit 04051005 |
| Permit Number |
04051005 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-10 00:00:00 | DENIED: | | | 1.PLEASE CLARIFY LOCATION & ACCESS TO | | | THE CONDENSING UNIT FOR THE NEW 3 TON | | | LIEBERT SYSTEM. | | | | | | 2.THE CONDENSING UNIT STAND SHALL HAVE | | | A MINIMUM CLEARANCE BETWEEN THE ROOF | | | SURFACE & THE BOTTOM OF THE SUPPORT RAIL | | | IN ACCORDANCE WITH 2001 FBC 1511.7 | | | (SEE ATTACHED). | | | | | | 3.PLEASE CLARIFY NEW OR EXISTING FIRE | | | DAMPERS. | | | | | | SEE ALSO COMMENT #2 BY DEWEY PALMER, | | | ELECTRICAL PLAN REVIEW. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|