| 2004-05-25 00:00:00 | 1) DEMOLITION, RENOVATION, AND |
| | CONSTRUCTION TO COMPLY WITH NFPA 241. |
| | |
| | 2) DEBRIS SHALL BE REMOVED FROM THE |
| | BUILDING DAILY. |
| | |
| | 3) ALL EXITWAYS SHALL REMAIN CLEAR |
| | AND ACCESSIBLE. |
| | |
| | 4) DOOR SWING APPEARS TO BE INCORRECT |
| | ON ONE OF THE EXISTING STAIRTOWERS. |
| | |
| | 5) PLEASE CLARIFY # 8 ON PAGE A211. |
| | ANY LOCKING DEVICES INSTALLED ON |
| | EXIT DOORS SHALL COMPLY WITH |
| | SPECIAL LOCKING ARRANGEMENTS AS PER |
| | THE 2000 EDITION OF THE LIFE SAFETY |
| | CODE. PLEASE PROVIDE MORE DETAILS. |
| | |
| | 6) WHAT FIRE RATING IS PRESENT FOR |
| | THE HERCULITE DOORS PLANNED FOR THE |
| | ELEVATOR LOBBY. |
| | |
| | 7) HOW IS FIRE RESCUE EXPECTED TO |
| | ENTER THE SPACE SHOULD THE FIRE ALARM |
| | SYSTEM OR SPRINKLER SYSTEM NOT BE |
| | OPERATING WITH THE PROPOSED INSTALLATION |
| | OF SECURITY DEVICES. |
| | |
| | 8) PLEASE SHOW ALL REQUIRED DIMENSIONS |
| | BETWEEN WORK STATIONS THAT WILL BE |
| | USED FOR EXITING. |
| | |
| | 9) FIRE ALARM NOTES # 16 AND # 18 |
| | ARE INCORRECT. FIRE ALARM CIRCUITS |
| | SHALL BE CLASS A, STYLE D AND DUCT |
| | SMOKE DETECTORS WHEN ACTIVATED SHALL |
| | INITIATE AN ALARM CONDITION NOT A |
| | TROUBLE CONDITION. PLEASE REVISE |
| | PLANS. |
| | |
| | 10) NO MANUAL PULL STATION NOTED AT |
| | EXIT STAIR NEAR COPY AREA. SEPARATE |
| | PLANS AND PERMITS REQUIRED FOR |
| | FIRE ALARM SYSTEM REMODEL. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |