| Plan Review Notes For Permit 04051005 |
| Permit Number |
04051005 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-18 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)FBC412.8.1, ALL STAIRWAY DOORS | | | WHICH ARE TO BE LOCKED FROM THE STAIR- | | | WAY SIDE SHALL HAVE THE CAPABILITY OF | | | BEING UNLOCKED UPON ACTIVITION OF THE | | | SPRINKLER SYSTEM OR UPON POWER FAILURE. | | | | | | 2.)DOOR 902 IS TO COMPLY WITH | | | FBC FIG 25, CHAPTER 11 (MANEUVERABILITY) | | | | | | 3.)SEE OTHER REVIEWER'S COMMENTS IN | | | REGARDS TO TITLE BLOCK ISSUES. | | | | | | 4.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. |
|