2004-06-16 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALL-ED. MAINS/BRKRS AND PANELS ARE
 ALL TO BERATED FOR THE AVAILABLE FAULT
 CURRENT.
 PER 110.9.
  
 2} THE DRYER IS NOT INCLUDED IN THE
 LOADCALCULATION AS REQUIRED PER 220.18.
  
 3} THE AHU LISTED IN THE LOAD
 CALCULATION IS 6000VA, BUT ON THE PANEL
 SCHEDULE IT IS ON A 20 AMP BREAKER
 LISTED AS FAN. THE HEAT STRIPS MUST BE
 INCLUDED, SEE THE NAMEPLATE RATING AND
 CORRECT THE PLAN.
  
 4} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.11C3
  
 5} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 6} THE RECEPTACLE PLACEMENT AND SPACING
 IN THE KITCHEN IS STILL INCORRECT,
 PLEASE READ 210.52 2002 NEC. IN ITS
 ENTIRETY
  
 7} PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE, SEVERAL AREAS
 ARE STILL NOT IN COMPLIANCE AS
 INDICATED IN THE PREVIOUS REVIEW.
  
 8} SHOW THE LOCATION OF THE A/C
 EQUIPMENT AND THE RECEPTACLES REQUIRED
 BY 210.63.
  
 9} SUBMIT 2(TWO) SETS OF PLANS FOR
 REVIEW PER 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026