| 2004-06-16 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALL-ED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BERATED FOR THE AVAILABLE FAULT |
| | CURRENT. |
| | PER 110.9. |
| | |
| | 2} THE DRYER IS NOT INCLUDED IN THE |
| | LOADCALCULATION AS REQUIRED PER 220.18. |
| | |
| | 3} THE AHU LISTED IN THE LOAD |
| | CALCULATION IS 6000VA, BUT ON THE PANEL |
| | SCHEDULE IT IS ON A 20 AMP BREAKER |
| | LISTED AS FAN. THE HEAT STRIPS MUST BE |
| | INCLUDED, SEE THE NAMEPLATE RATING AND |
| | CORRECT THE PLAN. |
| | |
| | 4} PLEASE LIST ALL THE REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.11C3 |
| | |
| | 5} PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 6} THE RECEPTACLE PLACEMENT AND SPACING |
| | IN THE KITCHEN IS STILL INCORRECT, |
| | PLEASE READ 210.52 2002 NEC. IN ITS |
| | ENTIRETY |
| | |
| | 7} PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE, SEVERAL AREAS |
| | ARE STILL NOT IN COMPLIANCE AS |
| | INDICATED IN THE PREVIOUS REVIEW. |
| | |
| | 8} SHOW THE LOCATION OF THE A/C |
| | EQUIPMENT AND THE RECEPTACLES REQUIRED |
| | BY 210.63. |
| | |
| | 9} SUBMIT 2(TWO) SETS OF PLANS FOR |
| | REVIEW PER 104.2.1 FBC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |