2004-05-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 2} PLEASE SUPPLY A LOAD CALCULATION PER
 220.30 NEC 2002.
  
 3} SUPPLY A PANEL SCHEDULE LISTING ALL
 REQUIRED CIRCUITS,RATING OF OVERCURRENT
 DEVICES AND CONDUCTOR SIZES.
  
 4} SHOW COMPLIANCE FOR GROUNDING ON THE
 RISER DIAGRAM PER 250.50 & 250.66.
  
 5} SHOW ALL LIGHTING IN COMPLIANCE WITH
 210.70 NEC.
  
 6} SHOW CABINET AND SINK LAYOUT IN THE
 KITCHEN AND BATH FOR COMPLIANCE WITH
 210.52(D) AND 210.52(C) &
 210.52(A)(1)&(2).
  
 7} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 8} PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6',12'RULE, CHECK ENTIRE
 DRAWING FOR NON COMPLIANCE.
  
 9} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.SEE 8-1.4.1.6.2 NFPA-72 1999
 FOR REQUIREMENTS.
  
 10} PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.210.52(E).
  
 11} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 THERE ARE SEVERAL DISCREPANCIES ON
 THESE PLANS. PLEASE READ NFPA-70 (NEC) &
 NFPA-72 BEFORE RESUBMITTING PLANS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW