| Date |
Text |
| 2004-06-15 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) PERMIT APPLICATION STATES 5 BAYS, THE |
| | PLANS SHOW 6 BAYS. CORRELATE APPLICATION |
| | WITH PLANS. |
| | 2) THE PERSNOAL SIGNATURE OF THE ARCHIT- |
| | ECT SHALL APPEAR ON THE DOCUMENTS TO BE |
| | FILED FOR PUBLIC RECORD. INITIALS ARE |
| | NOT ACCEPTABLE. FAC 61G1-16.003 & FS |
| | 481.2055. |
| | 3) SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS. SECTIONS 1106 & |
| | 1107. SHOW SQUARE FOOTAGE OF ROOF AND |
| | SHOW 1/2 AREA OF ALL VERTICAL WALLS IN- |
| | CLUDING PARAPETS ADDED TO AREA OF ROOF. |
| | INDICATE SLOPE OF GUTTERS PER TABLE |
| | 1106.6 AND SHOW HIGH POINTS OF GUTTER. |
| | 4) INDICATE THE OCCUPANCIES OF THE BAYS. |
| | TABLE 403.1 WILL DETERMINE WHICH FIXTUR- |
| | ES WILL BE REQUIRED ACCORDING TO THE |
| | OCCUPANCY OF EACH SPACE. DRINKING FOUNT- |
| | AINS SHALL BE REQUIRED FOR EACH SPACE. |
| | SEE SECTION 410.1. |
| | 5) SHT P-1 PLUMBING NOTES: |
| | #4 DIELECTRIC UNIONS ARE NOT APPROVED |
| | FOR WATER DISTRIBUTION. DELETE REFERENCE |
| | OR MODIFY TO READ DIELECTRIC COUPLING. |
| | #6 AIR CHAMBERS ARE NOT APPROVED. DE- |
| | LETE FROM REFERENCE. SECTION 604.9 |
| | 6) AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE. SECTION 608.13.2 |
| | 7) A WATER RISER DIAGRAM ISOMETRIC IS |
| | REQUIRED. SECTION 104.3.1.1. |
| | 8) OTHER COMMENTS MAY FOLLOW WHEN THE |
| | OCCUPANCY IS ESTABLISHED. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |