| 2004-06-02 00:00:00 | ********* UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE PLANS CONTAIN A TITLE |
| | BLOCK FOR AN ENGINEER ON ELECTRICAL |
| | PLANS. IF THIS PERSON(ENG) IS RESPON- |
| | -SIBLE FOR PLANS, PLANS MUST BE SIGNED |
| | AND SEALED BY THAT PERSON. FS 471/481 |
| | PLANS MUST ALSO CONTAIN A CLEAR AND |
| | RAISED SEAL. |
| | PLEASE SEE FS 471.025 AND FS 481.221 |
| | WHICH REQUIRES A 'SIGNATURE'. |
| | PLEASE PROVIDE A SIGNED, SEAL NOTARIZED |
| | LETTER FOR PROOF OF LEGAL SIGNATURE. |
| | |
| | 2)NOTE: PLEASE CORRELATE PERMIT APPL- |
| | -CATION AND PLANS. APPL MENTIONS 5 UNITS |
| | AND PLANS SHOW 6 UNITS? |
| | |
| | 3)NOTE: PLEASE COMPLETE RISER DIAGRAM. |
| | MISSING INFORMATION FOR MAIN(S). |
| | 230.72,230.76,230.79 ETC |
| | MISSING CONDUITS/CONDUCTORS ETC. |
| | 215.5/310.16 ETC |
| | |
| | 4)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | SYSTEM PER 250.50. |
| | EQUIPMENT GROUNDING CONDUCTORS PER 250. |
| | 122. |
| | |
| | 5)NOTE: PLEASE SEE OCP SHOWN FOR RECEPTS |
| | ON PANEL SCHEDULE. 80A?? |
| | |
| | 6)NOTE: PLEASE CORRELATE OCP SHOWN FOR |
| | A/C UNITS WITH MECH PLANS. |
| | |
| | 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 8 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | |
| | 9)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- |
| | -ING OF EM/EXT LTS. |
| | |
| | PLANS NOT COMPLETE AT THIS TIME FOR A |
| | FULL AND COMPLETE REVIEW. |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT ONLY NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | AS THEY MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |