2004-06-02 00:00:00NO MECHANICAL PLANS SUBMITTED. THE
 COMPLETED FORM 600C INDICATES CENTRAL
 AIR 12 SEER 240 SQ FT ADDITION.PLEASE
 PROVIDE THE FOLLOWING WITH MECHANICAL
 PERMIT APPLICATION:
  
 1.EQUIPMENT SCHEDULE INDICATE NEW OR
 EXISTING.
 2.PROVIDE DUCT/GRILLE SIZE, MATERIAL,
 AND LAYOUT.
  
 PLEASE NOTE RETURN AIR REQUIRED FROM THE
 NEW MUSIC ROOM PER 2001 FBC(M) 601.4.
  