| 2004-07-26 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE AIC RATING MARKED IN THE PANEL IS |
| | 10000, AND 22000 NOTED ON PLAN, PLEASE |
| | CORRELATE. |
| | |
| | 2} PLEASE SHOW THE LOCATION OF THE |
| | SERVICE EQUIPMENT ON THE PLAN. |
| | |
| | 3} THE PANEL SCHEDULE CONTAINS THE |
| | FOLLOWING VIOLATIONS: |
| | A) DINING ROOM CIRCUIT ON 15 AMP CKT. |
| | MUST COMPLY WITH 210.52(B)(1). |
| | B) THE 15 AMP SMALL APPLIANCE (KITCHEN) |
| | MUST COMPLY WITH 210.11(C)(1), 20 AMP. |
| | C) THE BATH CIRCUITS MUST COMPLY WITH |
| | 210.11(C)(3). |
| | D) THE WASHER/DRYER IS LISTED AS A |
| | SINGLE UNIT BUT SHOWN AS SEPARATE |
| | UNITS. PLEASE CORRELATE AND ADJUST |
| | LOAD CALCULATIONS ACCORDINGLY. |
| | |
| | 4} THE BACK BATHROOM (WHICH DOES NOT |
| | APPEAR ON THE ARCHITECTURAL PLAN A-1) |
| | MUST HAVE A RECEPTACLE TO COMPLY WITH |
| | 210.52(D)., ALSO CORRELATE PLANS TO |
| | INDICATE IF THAT ROOM IS TO BE PART OF |
| | THIS PLAN. |
| | |
| | 5} THE RECEPTACLE SPACING IN THE |
| | DINING,AND BACK BEDROOM IS IN VIOLATION |
| | OF 210.52(A)(1). |
| | |
| | 6} THE KITCHEN RECEPTACLES MUST COMPLY |
| | WITH 210.52(C)(1) SPACING AND |
| | 210.8(A)(6) GFI. |
| | |
| | 7} SMOKE DETECTORS ARE REQUIRED PER 8-1. |
| | 4.1.6.2 NFPA-72. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |