| 2004-10-29 00:00:00 | DENIED |
| | |
| | 1) ACCORDING TO THE PROPERTY APPRAISER,S |
| | RECORDS THIS PARCEL IS OWNED BY A |
| | CORPORATION. THEREFORE, A CONTRACTOR IS |
| | REQUIRED. NO OWNER BUILDER PERMIT CAN BE |
| | ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 4) CORRECT THE BUILDING TYPE SPECIFIED |
| | ON SHEET SP2. TYPE IV BUILDINGS ARE NOT |
| | ALLOWED TO HAVE WOOD TRUSSES. SEE FBC |
| | CHAPTER 6. |
| | |
| | 5) SUBMIT (2) COMPLETE COPIES OF THE |
| | SOIL REPORT WITH BORING LOGS SIGNED AND |
| | SEALED BY THE SOIL ENGINEER. |
| | |
| | 6) THE STRUCTURE IS LOCATED IN AN A5 |
| | FLOOD ZONE AN ELEVATION CERTIFICATE WILL |
| | BE REQUIRED. |
| | |
| | 7) CITY AMENDMENTS TO FBC TABLE 2306.1 |
| | REQUIRES RING SHANK NAILS IN ZONE 3 FOR |
| | FASTENING ROOF SHEATHING. PLEASE REVISE |
| | THE NOTE ON S5. |
| | |
| | 8) THE RED LINED CHANGES TO NOTE WT 3 |
| | ARE REQUIRED TO BE INITAILED AND DATED |
| | BY THE P.E. |
| | |
| | 9) REVISE THE TRUSS DESIGN CRITERIA ON |
| | S5 TO AGREE WITH INFO ON SHEET SN. |
| | |
| | 10) UPDATE THE MASONRY STANDARDS ON SN1 |
| | TO THE 2002 EDITIONS THAT ARE REFERENCED |
| | IN THE 2001 FBC CHAPTER 35(AMENDMENTS). |
| | |
| | 11) THE CLEAR OPENING SIZES OF THE BED |
| | ROOM WINDOWS DO NOT APPEAR TO COMPLY |
| | WITH REQUIREMENTS OF FBC 1005.4 FOR |
| | EMERGENCY EGRESS. PLEASE CALL OUT THE |
| | WINDOW SIZES SEPARATELY FROM THE FIXED |
| | HALF CIRCLE WINDOWS THAT ARE ATTACHED |
| | ABOVE THEM WITH MULLIONS. |
| | |
| | 12) PLANS SHOW A MASONRY FIREPLACE AND |
| | CHIMNEY. THE PLAN NOTES REFER TO A |
| | PREFABRICATED FIREPLACE AND CHIMNEY. |
| | PLEASE CLARIFY. IF IT IS PREFAB SUBMIT |
| | THE MANUFACTURER'S SPECIFICATIONS AND |
| | LISTING. IF IT IS A SITE CONSTRUCTED |
| | MASONRY FIREPLACE AND CHIMNEY SUBMIT |
| | DETAILED DRAWINGS WITH ALL DIMENSIONS |
| | FOR FIREBOX DEPTH, FIREPLACE OPENING, |
| | SMOKE CHAMBER, FLUE, ETC. SEE FBC 2804 & |
| | 2806 FOR PREFAB AND FBC 2113 & 2114 FOR |
| | SITE CONSTRUCTED MASONRY. |
| | |
| | 13) SPECIFY THE REINFORCING IN THE |
| | FIREPLACE FOUNDATION. |
| | |
| | 14) PLEASE CORRECT NOTE 6 ON S3 THAT HAS |
| | TYPE OVER IT. |
| | |
| | 15) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | SUBMIT PRODUCT APPROVALS FOR WINDOWS, |
| | DOORS, ROOFING, OVERHEAD GARAGE DOORS, |
| | STORM PANELS, TRUSS CONNECTORS, ETC. |
| | |
| | 16) THE OWNER/AGENT IS REQUIRED TO SIGN |
| | THE ENERGY CALCULATION FORMS. |
| | |
| | 17) THE CONDITIONED AREA LISTED ON THE |
| | ENERGY CALCULATION FORM DOES NOT MATCH |
| | THE LIVING AREA SQUARE FOOTAGE LISTED ON |
| | THE PLAN. PLEASE CORRECT. |
| | |