| Plan Review Notes For Permit 04050928 |
| Permit Number |
04050928 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-14 00:00:00 | DENIED: | | | 1.RETURN AIR FROM THE MASTER BEDROOM | | | INDICATED ON THE 1ST FLOOR IS NOT SIZED | | | PROPERLY.ALL AIR INTO THE MASTER | | | SUITE IS TO BE INCLUDED FOR A "TOTAL" | | | OF SUPPLY AIR INTO THE SUITE.THE | | | RETURN AIR JUMPER SHALL BE A MINIMUM OF | | | 1 1/2 TIMES THE TOTAL OF SUPPLY AIR. | | | SEE THE ATTACHED SCHEDULE. | | | | | | 2.PLAN SHEET M1.01, RETURN AIR INTO | | | THE LIVING AREA - NO DUCT SIZE INDICATED | | | IS THIS RETURN AIR FROM AHU 3, PLEASE | | | CLARIFY. | | | | | | 3.RETURN AIR REQUIRED FOM BEDROOM #2 | | | & 2ND FLOOR MASTER BEDROOM. | | | | | | 4.PLAN SHEET M2.01 VENTILATION NOTE | | | INDICATES PER TABLE 403.3.PLEASE | | | INDICATE FRESH AIR INTAKE, DUCT SIZE | | | AND MATERIAL.PLEASE NOTE, FRESH AIR | | | SHALL NOT BE TAKEN FROM THE ROOF TOP IN | | | A RESIDENTIAL APPLICATION PER 2001 FBC | | | CHAPTER 13 SUB-CHAPTER 609.1.1BC.1 #2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|