Plan Review Notes
Plan Review Notes For Permit 04050928
Permit Number 04050928
Review Stop M
Sequence Number 1
Notes
Date Text
2004-06-14 00:00:00DENIED:
 1.RETURN AIR FROM THE MASTER BEDROOM
 INDICATED ON THE 1ST FLOOR IS NOT SIZED
 PROPERLY.ALL AIR INTO THE MASTER
 SUITE IS TO BE INCLUDED FOR A "TOTAL"
 OF SUPPLY AIR INTO THE SUITE.THE
 RETURN AIR JUMPER SHALL BE A MINIMUM OF
 1 1/2 TIMES THE TOTAL OF SUPPLY AIR.
 SEE THE ATTACHED SCHEDULE.
  
 2.PLAN SHEET M1.01, RETURN AIR INTO
 THE LIVING AREA - NO DUCT SIZE INDICATED
 IS THIS RETURN AIR FROM AHU 3, PLEASE
 CLARIFY.
  
 3.RETURN AIR REQUIRED FOM BEDROOM #2
 & 2ND FLOOR MASTER BEDROOM.
  
 4.PLAN SHEET M2.01 VENTILATION NOTE
 INDICATES PER TABLE 403.3.PLEASE
 INDICATE FRESH AIR INTAKE, DUCT SIZE
 AND MATERIAL.PLEASE NOTE, FRESH AIR
 SHALL NOT BE TAKEN FROM THE ROOF TOP IN
 A RESIDENTIAL APPLICATION PER 2001 FBC
 CHAPTER 13 SUB-CHAPTER 609.1.1BC.1 #2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved