Plan Review Notes
Plan Review Notes For Permit 04050928
Permit Number 04050928
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-02 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE ARE TWO ROOMS LABELED "MASTER
 BEDROOM", PLEASE MAKE CLARIFICATION FOR
 CIRCUITING ON PANEL SCHEDULES.
  
 2} THE DISCONNECTS FOR THE CONDENSERS
 DO NOT COMPLY WITH 110.26 FOR SPACING,
 PLEASE RELOCATE TO COMPLY WITH SAME AND
 440.14.
  
 3} ALTHOUGH NOTE #2 ON SHEET E1.01
 INDICATES INTERCONNECTED SMOKE
 DETECTORS REQUIRED BY NFPA-72 & FBC
 905.2, THE CIRCUIT DESIGNATIONS FOR
 A-18 & B-18 INDICATE TWO SEPARATE
 SOURCES OF POWER. PLEASE CLARIFY.
  
 4} ALSO NOTE THAT 210.12 STATES
 THAT ALL OUTLETS BE AFCI PROTECTED.
 THAT INCLUDES SMOKE DETECTORS LOCATED
 IN DWELLING UNIT BEDROOMS.
  
 5} THE RECEPTACLE LOCATED IN THE ATTIC
 ABOVE THE WALK IN CLOSET CANNOT BE ON
 THE BATH RECEPTACLE CIRCUIT PER
 210.11(C)(3). SHEET E1.02.
  
 6} THE SMOKE DETECTOR LOCATED IN THE
 HALLWAY OUTSIDE THE MASTER BEDROOM ON
 SHEET E1.02 MUST BE MOVED TO THE INSIDE
 OF THE ROOM (OTHER SIDE OF THE BUKHEAD)
 TO COMPLY WITH 8-1.4.1.6 NFPA-72.
  
 7} THERE IS A RECEPTACLE IN THE MASTER
 BEDROOM ON CIRCUIT B-26, THIS IS NOT AN
 ARC FAULT PROTECTED CIRCUIT PER THE
 PANEL SCHEDULE, AND THEREFORE DOES NOT
 COMPLY WITH 210.12.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026