| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THERE ARE TWO ROOMS LABELED "MASTER |
| | BEDROOM", PLEASE MAKE CLARIFICATION FOR |
| | CIRCUITING ON PANEL SCHEDULES. |
| | |
| | 2} THE DISCONNECTS FOR THE CONDENSERS |
| | DO NOT COMPLY WITH 110.26 FOR SPACING, |
| | PLEASE RELOCATE TO COMPLY WITH SAME AND |
| | 440.14. |
| | |
| | 3} ALTHOUGH NOTE #2 ON SHEET E1.01 |
| | INDICATES INTERCONNECTED SMOKE |
| | DETECTORS REQUIRED BY NFPA-72 & FBC |
| | 905.2, THE CIRCUIT DESIGNATIONS FOR |
| | A-18 & B-18 INDICATE TWO SEPARATE |
| | SOURCES OF POWER. PLEASE CLARIFY. |
| | |
| | 4} ALSO NOTE THAT 210.12 STATES |
| | THAT ALL OUTLETS BE AFCI PROTECTED. |
| | THAT INCLUDES SMOKE DETECTORS LOCATED |
| | IN DWELLING UNIT BEDROOMS. |
| | |
| | 5} THE RECEPTACLE LOCATED IN THE ATTIC |
| | ABOVE THE WALK IN CLOSET CANNOT BE ON |
| | THE BATH RECEPTACLE CIRCUIT PER |
| | 210.11(C)(3). SHEET E1.02. |
| | |
| | 6} THE SMOKE DETECTOR LOCATED IN THE |
| | HALLWAY OUTSIDE THE MASTER BEDROOM ON |
| | SHEET E1.02 MUST BE MOVED TO THE INSIDE |
| | OF THE ROOM (OTHER SIDE OF THE BUKHEAD) |
| | TO COMPLY WITH 8-1.4.1.6 NFPA-72. |
| | |
| | 7} THERE IS A RECEPTACLE IN THE MASTER |
| | BEDROOM ON CIRCUIT B-26, THIS IS NOT AN |
| | ARC FAULT PROTECTED CIRCUIT PER THE |
| | PANEL SCHEDULE, AND THEREFORE DOES NOT |
| | COMPLY WITH 210.12. |
| | |