| 2004-06-22 00:00:00 | DENIED |
| | |
| | ROBERT KNOTH IS NOT THE CURRENT OWNER OF |
| | RECORD. RECORDS INDICATE THAT PROPERTY |
| | WAS SOLD IN JANURARY 2004 TO AQUA VISTA |
| | LLC. OWNER BUILDER PERMIT CAN NOT BE |
| | ISSUED TO A CORPORATION. IF THIS INFORM- |
| | ATION IS INCORRECT, SUBMIT PROOF OF |
| | CURRENT OWNERSHIP. |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT AN ADDITIONAL COPY OF THE SOIL |
| | REPORT. SUBMIT (2) COPIES OF THE SOIL |
| | BORING LOGS. |
| | |
| | 4) THE STRUCTURE IS LOCATED IN AN A5 |
| | FLOOD ZONE AND IS REQUIRED TO HAVE THE |
| | FINISH FLOOR ELEVATION 6" ABOVE BASE |
| | FLOOD ELEVATION. SPECIFY ELEVATION ON |
| | THE PLANS. AN ELEVATION CERTIFICATE WILL |
| | BE REQUIRED PRIOR TO C.O. |
| | |
| | 5) THE CITY OF WPB AMENDMENTS TO FBC |
| | TABLE 2306.1 REQIRE 8D RING SHANK NAILS |
| | IN ZONE 3 FOR STRUCTURES WITH MEAN ROOF |
| | HEIGHTS OF 25'-35'. PLEASE REVISE NOTE |
| | ON S5. |
| | |
| | 6) REVISE ROOF ROOF TRUSS DESIGN CRITERA |
| | CRITERIA ON S5. BOTTOM CORD LIVE LOAD IS |
| | REQUIRED TO BE 10PSF FOR ATTICS WITHOUT |
| | STORAGE PER FBC TABLE 1604.1. |
| | |
| | 7) SPECIFY THE POSITIVE AND NEGATIVE |
| | DESIGN PRESSURES FOR THE WINDOWS AND |
| | DOORS. |
| | |
| | 8) THE MASONRY OPENING SIZES FOR WINDOWS |
| | IN THE SCHEDULE ON A14 DO NOT CORRESPOND |
| | TO STANDARD WINDOW SIZES. PLEASE REVIEW. |
| | SPECIFY THE CALL SIZES FOR THE WINDOWS |
| | SUCH AS SH25. WINDOWS MUST MEET EGRESS |
| | REQUIREMENTS OF FBC 1005.4. |
| | |
| | 9) PROVIDE DETAILS FOR FIREPLACE AND |
| | CHIMNEY CONSTRUCTION. SPECIFY FRAMING |
| | MATERIALS, SPACING, CONNECTORS, ETC. |
| | SPECIFY THE HEIGHT OF THE CHIMNEY ABOVE |
| | THE ROOF. SUBMIT THE MANUFACTURER'S |
| | SPECIFICATIONS AND UL OR OTHER LISTING |
| | INFORMATION FOR THE PREFAB FIREPLACE AND |
| | FLUE PIPE. |
| | |
| | 10) REVISE SECTIONS ON A10 TO SHOW FIRE |
| | BLOCKING AT DROP CEILINGS PER FBC 2305.1 |
| | |
| | 11) CORRECT TYPO AT SCREEN VENT DETAILS. |
| | SHOULD BE OUTER MOST NOT CUTTER MOST. |
| | |
| | 12) PROVIDE DETAILS OF THE INTERIOR |
| | GUARDRAIL/3'6" HIGH PARTITION WALL AT |
| | THE STAIRS, LANDING AND HALLWAY. |
| | |
| | 13)FBC 1007.8.3 REQUIRES CIRCULAR STAIRS |
| | TO HAVE A MINIMUM TREAD DEPTH OF 9" WITH |
| | 1" OF NOSING AT THE SMALLEST DIMENSION. |
| | CLARIFY THIS ON THE PLAN. |
| | |
| | 14) REVISE STAIR DETAIL (2) ON A12. |
| | HUGHES IS NO LONGER IN BUSINESS AND DO |
| | NOT HAVE STATE PRODUCT APPROVAL. SPECIFY |
| | ANOTHER CONNECTOR. |
| | |
| | 15) SPECIFY FIREBLOCKING AT THE TOP AND |
| | AND BOTTOM OF STAIR RUNS AS REQUIRED BY |
| | FBC 2305.1.3(3). |
| | |
| | 16) REVISE BALAUSTERS DETAIL ON A12. FBC |
| | 1015.3 REQUIRES INTERMEDIATE RAILS OR |
| | ORNAMENTAL PATTERN SUCH THAT A 4" |
| | DIAMETER SPHERE CAN NOT PASS THROUGH ANY |
| | OPENING UP TO A HEIGHT OF 34". A BOTTOM |
| | RAIL OR CURB SHALL BE PROVIDED THAT WILL |
| | REJECT PASSAGE OF A 2"DIAMETER SPHERE. |
| | SPECIFY THE HORIZONTAL REINFORCEMENT. |
| | SPECIFY THE SIZE OF THE VERTICAL |
| | REINFORCEMENT. SPECIFT THE EMBED DEPTH |
| | OF THE REINFORCING. SPECIFY HOW THE |
| | RAIN WATER WILL BE DRAINED FROM THE |
| | BALCONY. SHOP DRAWINGS WILL BE REQUIRED. |
| | |
| | 17) SPECIFY THE DIAMETER OF THE TAP CON |
| | SCREWS ON THE SLIDING GLASS DOOR DETAIL |
| | (10) ON A13. DRAWING SHOULD SHOW |
| | FASTENERS FOR FRAME THROUGH THE 1X4 AND |
| | INTO THE SUBSTRATE AS REQUIRED BY FBC |
| | 1707.4.4.2. |
| | |
| | 18) REVISE EXTERIOR DOOR DETAIL (7) ON A |
| | 13. FASTENERS FOR THE DOOR FRAME ARE |
| | REQUIRED TO GO THROUGH THE 1X BUCK AND |
| | INTO THE SUBSTRATE PER 1707.4.4.2. FRAME |
| | CAN ATTACH DIRECTLY TO 2X BUCKS. |
| | |
| | 19) THE DOOR AND WINDOW BUCK NOTE 5 |
| | UNDER DOORS AND WINDOWS ON A14 DOES NOT |
| | CORRESPOND TO BUCK DETAILS ON A13. |
| | PLEASE REVISE. |
| | |
| | 20) SPECIFY ON THE PLANS THAT THE |
| | STRUCTURE IS DESIGNED AS ENCLOSED, OPEN |
| | OR PARTICALLY ENCLOSED. SPECIFY THE |
| | INTERNAL PRESSURE COEFFICENT. |
| | |
| | 21) REVISE WOOD TRUSS NOTE WT3 ON SN. |
| | THE BOTTOM CORD LIVE LOAD IS REQUIRED TO |
| | BE 10 PSF FOR ATTICS WITHOUT STORAGE PER |
| | FBC TABLE 1604.1. |
| | |
| | 22) THE I.D. MARK ON S3 FOR THE SECTION |
| | 7/S4 IS IN THE WRONG LOCATION. PLEASE |
| | CORRECT. SEE MARKS ON PLAN. |
| | |
| | 23) THE BALCONY PEIRS ARE LABELED AS MP1 |
| | ON S3 AND MC1 ON S7. PLEASE CORRECT. |
| | |
| | 24) ON THE TRUSS ANCHOR SCHEDULE ON S7 T |
| | HE UPLIFT CAPACITIES FOR THE META 16 (C) |
| | AND HETA 20 (E) ARE HIGHER THAN THE |
| | 2004 CATALOG VALUES THAT DO NOT INCLUDE |
| | THE ONE-THIRD INCREASE ON THE STEEL |
| | CALCULATIONS. PLEASE REVISE. |
| | |
| | 25) ON S1 THE TC3 COLUMN IS SPECIFIED ON |
| | THE SOUTH ELEVATION BETWEEN THE TWO |
| | WINDOWS WHICH ARE 10" APART. SHOULD THIS |
| | BE A TC1 COLUMN. |
| | |
| | 26) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | SUBMIT STATE PRODUCT APPROVALS FOR |
| | WINDOWS, DOORS, ROOFING, OVERHEAD |
| | GARAGE DOORS, STORM PANELS, TRUSS |
| | CONNECTORS, ETC. |
| | |
| | 27) THE OWNER AGENT IS REQUIRED TO SIGN |
| | THE ENERGY CALC. FORM. |
| | |