Notes
Date Text
2004-06-22 00:00:00DENIED
  
 ROBERT KNOTH IS NOT THE CURRENT OWNER OF
 RECORD. RECORDS INDICATE THAT PROPERTY
 WAS SOLD IN JANURARY 2004 TO AQUA VISTA
 LLC. OWNER BUILDER PERMIT CAN NOT BE
 ISSUED TO A CORPORATION. IF THIS INFORM-
 ATION IS INCORRECT, SUBMIT PROOF OF
 CURRENT OWNERSHIP.
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT AN ADDITIONAL COPY OF THE SOIL
 REPORT. SUBMIT (2) COPIES OF THE SOIL
 BORING LOGS.
  
 4) THE STRUCTURE IS LOCATED IN AN A5
 FLOOD ZONE AND IS REQUIRED TO HAVE THE
 FINISH FLOOR ELEVATION 6" ABOVE BASE
 FLOOD ELEVATION. SPECIFY ELEVATION ON
 THE PLANS. AN ELEVATION CERTIFICATE WILL
 BE REQUIRED PRIOR TO C.O.
  
 5) THE CITY OF WPB AMENDMENTS TO FBC
 TABLE 2306.1 REQIRE 8D RING SHANK NAILS
 IN ZONE 3 FOR STRUCTURES WITH MEAN ROOF
 HEIGHTS OF 25'-35'. PLEASE REVISE NOTE
 ON S5.
  
 6) REVISE ROOF ROOF TRUSS DESIGN CRITERA
 CRITERIA ON S5. BOTTOM CORD LIVE LOAD IS
 REQUIRED TO BE 10PSF FOR ATTICS WITHOUT
 STORAGE PER FBC TABLE 1604.1.
  
 7) SPECIFY THE POSITIVE AND NEGATIVE
 DESIGN PRESSURES FOR THE WINDOWS AND
 DOORS.
  
 8) THE MASONRY OPENING SIZES FOR WINDOWS
 IN THE SCHEDULE ON A14 DO NOT CORRESPOND
 TO STANDARD WINDOW SIZES. PLEASE REVIEW.
 SPECIFY THE CALL SIZES FOR THE WINDOWS
 SUCH AS SH25. WINDOWS MUST MEET EGRESS
 REQUIREMENTS OF FBC 1005.4.
  
 9) PROVIDE DETAILS FOR FIREPLACE AND
 CHIMNEY CONSTRUCTION. SPECIFY FRAMING
 MATERIALS, SPACING, CONNECTORS, ETC.
 SPECIFY THE HEIGHT OF THE CHIMNEY ABOVE
 THE ROOF. SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS AND UL OR OTHER LISTING
 INFORMATION FOR THE PREFAB FIREPLACE AND
 FLUE PIPE.
  
 10) REVISE SECTIONS ON A10 TO SHOW FIRE
 BLOCKING AT DROP CEILINGS PER FBC 2305.1
  
 11) CORRECT TYPO AT SCREEN VENT DETAILS.
 SHOULD BE OUTER MOST NOT CUTTER MOST.
  
 12) PROVIDE DETAILS OF THE INTERIOR
 GUARDRAIL/3'6" HIGH PARTITION WALL AT
 THE STAIRS, LANDING AND HALLWAY.
  
 13)FBC 1007.8.3 REQUIRES CIRCULAR STAIRS
 TO HAVE A MINIMUM TREAD DEPTH OF 9" WITH
 1" OF NOSING AT THE SMALLEST DIMENSION.
 CLARIFY THIS ON THE PLAN.
  
 14) REVISE STAIR DETAIL (2) ON A12.
 HUGHES IS NO LONGER IN BUSINESS AND DO
 NOT HAVE STATE PRODUCT APPROVAL. SPECIFY
 ANOTHER CONNECTOR.
  
 15) SPECIFY FIREBLOCKING AT THE TOP AND
 AND BOTTOM OF STAIR RUNS AS REQUIRED BY
 FBC 2305.1.3(3).
  
 16) REVISE BALAUSTERS DETAIL ON A12. FBC
 1015.3 REQUIRES INTERMEDIATE RAILS OR
 ORNAMENTAL PATTERN SUCH THAT A 4"
 DIAMETER SPHERE CAN NOT PASS THROUGH ANY
 OPENING UP TO A HEIGHT OF 34". A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT PASSAGE OF A 2"DIAMETER SPHERE.
 SPECIFY THE HORIZONTAL REINFORCEMENT.
 SPECIFY THE SIZE OF THE VERTICAL
 REINFORCEMENT. SPECIFT THE EMBED DEPTH
 OF THE REINFORCING. SPECIFY HOW THE
 RAIN WATER WILL BE DRAINED FROM THE
 BALCONY. SHOP DRAWINGS WILL BE REQUIRED.
  
 17) SPECIFY THE DIAMETER OF THE TAP CON
 SCREWS ON THE SLIDING GLASS DOOR DETAIL
 (10) ON A13. DRAWING SHOULD SHOW
 FASTENERS FOR FRAME THROUGH THE 1X4 AND
 INTO THE SUBSTRATE AS REQUIRED BY FBC
 1707.4.4.2.
  
 18) REVISE EXTERIOR DOOR DETAIL (7) ON A
 13. FASTENERS FOR THE DOOR FRAME ARE
 REQUIRED TO GO THROUGH THE 1X BUCK AND
 INTO THE SUBSTRATE PER 1707.4.4.2. FRAME
 CAN ATTACH DIRECTLY TO 2X BUCKS.
  
 19) THE DOOR AND WINDOW BUCK NOTE 5
 UNDER DOORS AND WINDOWS ON A14 DOES NOT
 CORRESPOND TO BUCK DETAILS ON A13.
 PLEASE REVISE.
  
 20) SPECIFY ON THE PLANS THAT THE
 STRUCTURE IS DESIGNED AS ENCLOSED, OPEN
 OR PARTICALLY ENCLOSED. SPECIFY THE
 INTERNAL PRESSURE COEFFICENT.
  
 21) REVISE WOOD TRUSS NOTE WT3 ON SN.
 THE BOTTOM CORD LIVE LOAD IS REQUIRED TO
 BE 10 PSF FOR ATTICS WITHOUT STORAGE PER
 FBC TABLE 1604.1.
  
 22) THE I.D. MARK ON S3 FOR THE SECTION
 7/S4 IS IN THE WRONG LOCATION. PLEASE
 CORRECT. SEE MARKS ON PLAN.
  
 23) THE BALCONY PEIRS ARE LABELED AS MP1
 ON S3 AND MC1 ON S7. PLEASE CORRECT.
  
 24) ON THE TRUSS ANCHOR SCHEDULE ON S7 T
 HE UPLIFT CAPACITIES FOR THE META 16 (C)
 AND HETA 20 (E) ARE HIGHER THAN THE
 2004 CATALOG VALUES THAT DO NOT INCLUDE
 THE ONE-THIRD INCREASE ON THE STEEL
 CALCULATIONS. PLEASE REVISE.
  
 25) ON S1 THE TC3 COLUMN IS SPECIFIED ON
 THE SOUTH ELEVATION BETWEEN THE TWO
 WINDOWS WHICH ARE 10" APART. SHOULD THIS
 BE A TC1 COLUMN.
  
 26) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 SUBMIT STATE PRODUCT APPROVALS FOR
 WINDOWS, DOORS, ROOFING, OVERHEAD
 GARAGE DOORS, STORM PANELS, TRUSS
 CONNECTORS, ETC.
  
 27) THE OWNER AGENT IS REQUIRED TO SIGN
 THE ENERGY CALC. FORM.
  
 IF YOU HAVE QUESTIONS PLEASE CALL: