 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SHOW THE GROUNDING ELECTRODE SYSTEM
 ON THE RISER DIAGRAM FOR COMPLIANCE
 WITH 250.50 & 250.66.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 3} INDICATE CONDUCTOR AND CONDUIT SIZE
 AND TYPE FOR THE SERVICE PER 230.41 &
 42.
  
 4} INDICATE THE MEANS OF DISCONNECT FOR
 THE SERVICE PER 230.70.
  
 5} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 6} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED.
  
 7} THE SMALL APPLIANCE CIRCUITS MUST BE
 CALCULATED @ 1500VA EACH PER 220.16(A).
  
 8} THERE MUST BEA DISCONNECTING MEANS AT
 THE A/C CONDENSER PER 440.14, AND A
 RECEPTACLE PER 210.63.
  
 9} A SMOKE DETECTOR MUST BE LOCATED IN
 THE SLEEPING ROOM PER 8-1.4.1.6.2
 NFPA-72.
  
 10} A RECEPTACLE MUST BE ADDED IN THE
 BEDROOM TO COMPLY WITH 210.52(A)(1)
 SPACING.
  
 11} THE DINING ROOM MUST BE ON A SMALL
 APPLIANCE CIRCUIT PER 210.52(B)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW