| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} SHOW THE GROUNDING ELECTRODE SYSTEM |
| | ON THE RISER DIAGRAM FOR COMPLIANCE |
| | WITH 250.50 & 250.66. |
| | |
| | 2} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALLED. MAINS/BRKRS AND PANELS ARE |
| | ALL TO BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT PER 110.9. |
| | |
| | 3} INDICATE CONDUCTOR AND CONDUIT SIZE |
| | AND TYPE FOR THE SERVICE PER 230.41 & |
| | 42. |
| | |
| | 4} INDICATE THE MEANS OF DISCONNECT FOR |
| | THE SERVICE PER 230.70. |
| | |
| | 5} PLEASE LIST ALL THE REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 6} PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED. |
| | |
| | 7} THE SMALL APPLIANCE CIRCUITS MUST BE |
| | CALCULATED @ 1500VA EACH PER 220.16(A). |
| | |
| | 8} THERE MUST BEA DISCONNECTING MEANS AT |
| | THE A/C CONDENSER PER 440.14, AND A |
| | RECEPTACLE PER 210.63. |
| | |
| | 9} A SMOKE DETECTOR MUST BE LOCATED IN |
| | THE SLEEPING ROOM PER 8-1.4.1.6.2 |
| | NFPA-72. |
| | |
| | 10} A RECEPTACLE MUST BE ADDED IN THE |
| | BEDROOM TO COMPLY WITH 210.52(A)(1) |
| | SPACING. |
| | |
| | 11} THE DINING ROOM MUST BE ON A SMALL |
| | APPLIANCE CIRCUIT PER 210.52(B)(1). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |