Notes
Date Text
2005-03-14 00:00:00PASSED/PROVISO
  
 SERVICE SINKS SHALL CONNECT DOWNSTREAM
 OF THE OF THE WET VENT. SECTION 909.1
  
 FULL OPEN VALVE REQUIRED ON THE WATER
 DISTRIBUTION SUPPPLY PIPE AT THE
 ENTRANCE INTO THE STRUCTURE.
  
 FULL OPEN VALVES SHALL BE INSTALLED ON
 ALL WATER DOWN-FEED PIPES. SECTION
 606.1(4)
  
 REVISION REQUIRED SHOWING CHANGES
  
  
  
  
  
  
  
  
 .