| Plan Review Notes For Permit 04050895 |
| Permit Number |
04050895 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-12-21 00:00:00 | ******* UNSAT ******** | | | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM | | | WIHT PANEL SCHEDULES AND PLANS. | | | PLEASE SEE PANEL SCHEDULE "A" DOES NOT | | | INDICATE OF THIS IS TYPICAL OF TWO? | | | PLEASE SEE BOTH PANEL "B" ON SCHEDULE | | | ARE SHOWN AS 150A AND YET RISER SHOWS | | | 100A. | | | PLEASE SEE PLANS INDICATE TWO PANEL "B" | | | IN ONE TENANT SPACE? | | | | | | 2)NOTE: PLEASE VERIFY BLDG FOOTER STEEL | | | IF PERMIT WAS FOR A NEW WAREHOUSE BLDG. | | | 250.50 | | | | | | 3)NOTE: PLEASE BE SURE THAT ALL | | | REVISIONS ARE LABELED, BY | | | CLOUDS/TRIANGLES AND LISTED IN THE TITLE | | | BLOCK. | | | | | | PLEASE SUBMIT THE ABOVE CORRECTIONS FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|