| 2005-01-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | COMMENTS FROM PREVIOUS REVIEWS: | | | 2) INDICATE OCCUPANCY OF EACH UNIT. THIS | | | IS REQUIRED TO DETERMINE MINIMUM | | | PLUMBING FACILITIES. DRINKING FOUNTAINS | | | ARE REQUIRED IN EACH SPACE. MORE | | | COMMENTS MAY FOLLOW ONCE OCCUPANCY IS | | | ESTABLISHED. TABLE 403.1. | | | 3) TOILET ROOMS SHALL COMPLY WITH | | | SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND | | | ALL SUBSECTIONS. DETAILS DO NOT SHOW | | | CLEAR FLOOR SPACE FOR W/C AND LAV, AND | | | EXPOSED PIPES AND SURFACES FOR LAV. | | | 4) A WATER RISER DIAGRAM IS REQUIRED PER | | | SECTION 104.3.1.1. | | | 1B) SHT E-1 PLUMBING NOTES: #14 AIR | | | CHAMBERS ARE NOT APPROVED. DELETE FROM | | | REFERENCE. SECTION 604.9 | | | *******NEW COMMENT********** | | | 1C) AS REQUIRED BY 104.3.1.1 OF THE CODE | | | TWO OR MORE COPIES OF DRAWINGS SHALL | | | ACCOMPANY THE APPLICATION FOR A PERMIT. | | | SHEET 5 OF 6 IS MISSING FROM EACH SET OF | | | PLANS RESUBMITTED 12-20-04. | | | 2C) SEE ATTACHED SHEET CONCERNING THE | | | DESIGN PROFESSIONAL AND FS | | | 553.80(2)(B). | | | | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|