Plan Review Notes
Plan Review Notes For Permit 04050895
Permit Number 04050895
Review Stop P
Sequence Number 3
Notes
Date Text
2005-01-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 COMMENTS FROM PREVIOUS REVIEWS:
 2) INDICATE OCCUPANCY OF EACH UNIT. THIS
 IS REQUIRED TO DETERMINE MINIMUM
 PLUMBING FACILITIES. DRINKING FOUNTAINS
 ARE REQUIRED IN EACH SPACE. MORE
 COMMENTS MAY FOLLOW ONCE OCCUPANCY IS
 ESTABLISHED. TABLE 403.1.
 3) TOILET ROOMS SHALL COMPLY WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS. DETAILS DO NOT SHOW
 CLEAR FLOOR SPACE FOR W/C AND LAV, AND
 EXPOSED PIPES AND SURFACES FOR LAV.
 4) A WATER RISER DIAGRAM IS REQUIRED PER
 SECTION 104.3.1.1.
 1B) SHT E-1 PLUMBING NOTES: #14 AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 REFERENCE. SECTION 604.9
 *******NEW COMMENT**********
 1C) AS REQUIRED BY 104.3.1.1 OF THE CODE
 TWO OR MORE COPIES OF DRAWINGS SHALL
 ACCOMPANY THE APPLICATION FOR A PERMIT.
 SHEET 5 OF 6 IS MISSING FROM EACH SET OF
 PLANS RESUBMITTED 12-20-04.
 2C) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS
 553.80(2)(B).
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]