Plan Review Notes
Plan Review Notes For Permit 04050895
Permit Number 04050895
Review Stop P
Sequence Number 2
Notes
Date Text
2004-09-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 COMMENTS FROM PREVIOUS REVIEW:
 2) INDICATE OCCUPANCY OF EACH UNIT. THIS
 IS REQUIRED TO DETERMINE MINIMUM PLUMB-
 ING FACILITIES. DRINKING FOUNTAINS ARE
 REQUIRED IN EACH SPACE. MORE COMMENTS
 MAY FOLLOW ONCE OCCUPANCY IS ESTABLISHED
 TABLE 403.1
 3) TOILET ROOMS SHALL COMPLY WITH SECT-
 IONS 11-4.16, 11-4.19, AND 11-4.22 AND
 ALL SUBSECTIONS.DETAIL DOES NOT SHOW
 CLEAR FLOOR SPACE FOR W/C AND LAV, FLUSH
 CONTROLS FOR W/C, EXPOSED PIPES AND SUR-
 FACES FOR LAV, AND DOORS TO ACCESSIBLE
 TOILET SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 4) A WATER RISER DIAGRAM IS REQUIRED PER
 SECTION 104.3.1.1
 ***********NEW COMMENTS**********
 1B) SHEET E-1 PLUMBING NOTES:
 #14 AIR CHAMBERS ARE NOT APPROVED.
 DELETE FROM REFERENCE. SECTION 604.9
 2B) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW SQUARE FOOT-
 AGE FOR ROOF AREAS AND SHOW 1/2 AREA OF
 ALL VERTICAL WALLS ADDED TO CALCULATIONS
 SHOW LOCATIONS OF PRIMARY AND SECONDARY
 ROOF DRAINS. SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved