| Plan Review Notes For Permit 04050895 |
| Permit Number |
04050895 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) DRAWINGS AND ACCOMPANYING DATA SHALL | | | BEAR THE NAME AND SIGNATURE OF THE PER- | | | SON RESPONSIBLE FOR THE DESIGN. SECTION | | | 104.2.1 | | | 2) INDICATE OCCUPANCY OF EACH UNIT. THIS | | | IS REQUIRED TO DETERMINE MINIMUM PLUMB- | | | ING FACILITIES. DRINKING FOUNTAINS ARE | | | REQUIRED IN EACH SPACE. MORE COMMENTS | | | MAY FOLLOW ONCE OCCUPANCY IS ESTABLISHED | | | TABLE 403.1. | | | 3) TOILET ROOMS SHALL COMPLY WITH SECT- | | | IONS 11-4.16, 11-4.19, AND 11-4.22 AND | | | ALL SUBSECTIONS. SUBMIT A DETAIL SHOWING | | | COMPLIANCE. SECTION 104.2.1. | | | 4) A WATER RISER DIAGRAM IS REQUIRED PER | | | SECTION 104.3.1.1. | | | 5) SHT E-1 THE SANITARY RISER DIAGRAM | | | DOES NOT REFLECT THE FLOOR PLAN. THE | | | LAVS AND WATER CLOSETS ARE BACK TO BACK | | | NOT NEXT TO EACH OTHER ON THE SAME WALL. | | | SUBMIT A RISER DIAGRAM THAT REFLECT THE | | | FLOOR PLAN. SECTION 104.2.1 & SECTION | | | 104.3.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|