Plan Review Notes
Plan Review Notes For Permit 04050895
Permit Number 04050895
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) DRAWINGS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE PER-
 SON RESPONSIBLE FOR THE DESIGN. SECTION
 104.2.1
 2) INDICATE OCCUPANCY OF EACH UNIT. THIS
 IS REQUIRED TO DETERMINE MINIMUM PLUMB-
 ING FACILITIES. DRINKING FOUNTAINS ARE
 REQUIRED IN EACH SPACE. MORE COMMENTS
 MAY FOLLOW ONCE OCCUPANCY IS ESTABLISHED
 TABLE 403.1.
 3) TOILET ROOMS SHALL COMPLY WITH SECT-
 IONS 11-4.16, 11-4.19, AND 11-4.22 AND
 ALL SUBSECTIONS. SUBMIT A DETAIL SHOWING
 COMPLIANCE. SECTION 104.2.1.
 4) A WATER RISER DIAGRAM IS REQUIRED PER
 SECTION 104.3.1.1.
 5) SHT E-1 THE SANITARY RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN. THE
 LAVS AND WATER CLOSETS ARE BACK TO BACK
 NOT NEXT TO EACH OTHER ON THE SAME WALL.
 SUBMIT A RISER DIAGRAM THAT REFLECT THE
 FLOOR PLAN. SECTION 104.2.1 & SECTION
 104.3.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved