Plan Review Notes
Plan Review Notes For Permit 04050895
Permit Number 04050895
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-05-21 00:00:001) BUILDING ADDRESS NOT SHOWN ON ANY
 ELEVATION. BUILDING ADDRESS IS REQUIRED.
 A MINIMUM OF 6" HIGH NUMBERS ARE
 REQUIRED.
  
 2) NO ILLUMINATED EXIT SIGNS OR
 EMERGENCY LIGHTS SHOWN ON ELECTRICAL
 PAGE.
  
 3) PLEASE INDICATE HOURLY RATING OF ANY
 FIRE RATED DEMISING WALL. PLEASE DISPLAY
 AN APPROPRIATE WALL DETAIL WITH UL
 NUMBER.
  
 4) PLEASE INDICATE LOCATIONS OF ANY
 EXISTING FIRE EXTINGUISHERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910