| 2004-05-28 00:00:00 | **************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE FBC 104.2.1 WHICH |
| | RQUIRES THE PRINTED NAME AND SIGNATURE |
| | OF PERSON RESPONSIBLE FOR PLANS. |
| | IF PLANS ARE DONE BY THE ENGINEER, |
| | PLEASE INCLUDE TITLE BLOCK, SIGNATURE, |
| | DATE AND SEAL. FS 471.025, FAC 61G15-23. |
| | 002. |
| | |
| | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. |
| | PLEASE VERIFY CIRCUITING DUE TO WHAT |
| | APPEARS TO BE TWO TENAT SPACES?? |
| | PLEASE SHOW LOCATION OF PANEL.NOTE:\ |
| | PANEL MAY NOT BE LOCATED IN ONE TENANT |
| | SPACE IF TWO SEPARATE TENANTS. ONLY A |
| | NOTE. |
| | BLDG PLANS NOTE TWO SEPARATE SPACES. |
| | |
| | 3)NOTE: PLEASE SEE FIRE REVIEW COMMENTS |
| | AND COMMENTS FROM OTHER REVIEWERS. |
| | THESE MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS FOR REVIEW AND |
| | STAMPING. |
| | ONE SET OF OLD SHEETS MAY BE REQUIRED |
| | FOR OTHER REVIEWS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |