| 2004-07-30 00:00:00 | CHECKLIST: |
| | 1-SPECIFY UL ASSEMBLY FOR ONE HR FIRE |
| | RATED GLASS BLOCK ASSEMBLY AT ZERO LOT |
| | LINE WALL. REVISE SPECIFICATIONS SHOWN |
| | ON DETAIL ON SHEET A-4 TO MATCH SUCH |
| | ASSEMBLY. SPECIFY FIRE RATED SEALANT |
| | AND GLASS BLOCK TYPE AND SIZE. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001 |
| | AND TABLE 600 FBC 2001. |
| | 2-SOIL TEST REPORT TO HAVE ORIGINAL |
| | SIGNATURES AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTES WHEN SUBMITTING |
| | DOCUMENTS FOR PUBLIC RECORDS. |
| | 3-PRODUCT APPROVAL FOR FIXED WINDOW: |
| | A)PROVIDE LEGIBLE DRAWINGS. |
| | B)DESIGN PRESSURES DON'T MEET THE DESIGN |
| | PRESSURES CALCULATED BY ENGINEER OF |
| | RECORD UNLESS USING TEMPERED GLASS. |
| | SPECIFY IF USING TEMPERED GLASS. |
| | C)NEED PRODUCT APPROVAL FOR LARGER |
| | WINDOWS AS SHOWN ON PLANS. |
| | |
| | 4-SUBMITTED FRENCH DOOR PRODUCT APPROVAL |
| | IS FOR OUTSWING DOORS. PLANS SHOW |
| | INSWING DOORS. NEED PRODUCT APPROVAL |
| | FOR INSWING DOORS OR REVISE PLANS. |
| | 5-PROVIDE PRODUCT APPROVAL FOR SLIDING |
| | GLASS DOORS WITH TRANSOM ABOVE SINGLE |
| | ASSEMBLY AS SHOWN ON PLANS. SEE PLANS. |
| | 6-PRODUCT APPROVAL FOR INSWING ENTRY |
| | DOOR W/ TRANSOM ABOVE SINGLE ASSEMBLY |
| | AS SOWN ON PLANS. |
| | 7-NEED PRODUCT APPROVAL FOR STRUCTURAL |
| | CONNECTORS SPECIFIED ON PLANS. |
| | 8-STORM SHUTTERS KEY PLAN SHOWS SHUTTERS |
| | ON ALL OPENINGS, BUT NEED TO PROVIDE |
| | EMERGENCY MEANS OF ESCAPE AS REQUIRED |
| | BY SEC. 1005.4.5 FBC 2001. SPECIFY ON |
| | PLANS WHICH OPENING WILL BE DEDICATED |
| | FOR EGRESS. |
| | 9-TRUSS DRAWING PACKAGE: |
| | A)ENGINEER TO PROVIDE ORIGINAL SIGNATURE |
| | AND DATE AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTES. |
| | B)TRUSS PACKAGE TO BE REVIEWED/APPROVED |
| | BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL TO THIS OFFICE. |
| | 10-WINDOW AND DOOR BUCK DETAILS: SHEET |
| | A-4 & SHEET S-3 SHOW DIFFERENT SPECS. |
| | CLARIFY WHICH METHOD WILL BE USED. |
| | 11-SHEET A5: REVISE/UPDATE NOTES. SEE |
| | CHAPTER 19 AND CHAPTER 35 FOR CORRECT |
| | STANDARDS AND EDITIONS TO BE USED. |
| | 12-CONNECTOR SPECIFIED FOR TRUSSES AT |
| | ATRIUM AREA DON'T RESIST CALCULATED |
| | LOADS SHOWN ON ENGINEERED TRUSSES. |
| | SEE ENGINEERED TRUSSES AND REVISE |
| | CONNECTORS AS REQUIRED. |
| | 13-HANGER HU614 IS FOR WOOD TO WOOD |
| | CONNECTIONS. NEED HANGER FOR WOOD TO |
| | MASONRY. REVISE AS REQ'D AND SPECIFY |
| | ALL FASTENERS. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 14-CONNECTOR SPECIFIED FOR TRUSSES ON |
| | TOP OF 2X12 WOOD BEAM AT REAR PORCH |
| | IS FOR WOOD TO MASONRY INSTALLATION. |
| | NEED WOOD TO WOOD CONNECTOR. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001 |
| | 15-WINDOWS AT DINING ROOM NEED TO BE |
| | SAFETY GLASS AS REQUIRED BY SECTION |
| | 2405.2.1(4) FBC 2001. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |