 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INCLUDE ALL LICENSE
 #'S ON THE REQUIRED TITLE BLOCK.
 PLEASE ALSO INCLUDE CERTIFICATE OF
 AUTHORIZATION #'S WHERE REQUIRED
 PER FS 471.023, FAC 61G15-23.002
 (ENG'S)PER FS 481.219, FAC 61G1-16.004
 THERE IS NO TITLE BLOCK ON THE PLANS.
  
 2} THE RISER INDICATES A 150 AMP
 CIRCUIT BREAKER PANEL WITH A 200 AMP
 DISCONNECT. SEE 408.16, OCP TOO LARGE
 FOR THE PANEL. THE 1/0 FEEDERS SHOWN
 MUST BE PROTECTED BY NOT MORE THAN A
 175 AMP BREAKER. PLEASE CORRECT THE
 RISER DIAGRAM.
  
 3} THE LAUNDRY CIRCUIT MUST COMPLY WITH
 220.11(C)(3),20AMPS,SEE PANEL SCHEDULE.
  
 4} THE KITCHEN COUNTERTOP RECEPTACLE
 SPACING MUST COMPLY WITH 210.52(C)(1).
  
 5} SMOKE DETECTORS MUST BE INSTALLED PER
 8-1.4.1.6.2 NFPA-72. PLEASE SHOW SAME
 ON PLANS.
  
 6} RECEPTACLE SPACING IN THE MASTER BED
 ROOM MUST COMPLY WITH 210.52. AT LEAST
 ONE RECEPTACLE MUST BE ADDED, SEE
 REVIEWED SET.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  