| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE INCLUDE ALL LICENSE |
| | #'S ON THE REQUIRED TITLE BLOCK. |
| | PLEASE ALSO INCLUDE CERTIFICATE OF |
| | AUTHORIZATION #'S WHERE REQUIRED |
| | PER FS 471.023, FAC 61G15-23.002 |
| | (ENG'S)PER FS 481.219, FAC 61G1-16.004 |
| | THERE IS NO TITLE BLOCK ON THE PLANS. |
| | |
| | 2} THE RISER INDICATES A 150 AMP |
| | CIRCUIT BREAKER PANEL WITH A 200 AMP |
| | DISCONNECT. SEE 408.16, OCP TOO LARGE |
| | FOR THE PANEL. THE 1/0 FEEDERS SHOWN |
| | MUST BE PROTECTED BY NOT MORE THAN A |
| | 175 AMP BREAKER. PLEASE CORRECT THE |
| | RISER DIAGRAM. |
| | |
| | 3} THE LAUNDRY CIRCUIT MUST COMPLY WITH |
| | 220.11(C)(3),20AMPS,SEE PANEL SCHEDULE. |
| | |
| | 4} THE KITCHEN COUNTERTOP RECEPTACLE |
| | SPACING MUST COMPLY WITH 210.52(C)(1). |
| | |
| | 5} SMOKE DETECTORS MUST BE INSTALLED PER |
| | 8-1.4.1.6.2 NFPA-72. PLEASE SHOW SAME |
| | ON PLANS. |
| | |
| | 6} RECEPTACLE SPACING IN THE MASTER BED |
| | ROOM MUST COMPLY WITH 210.52. AT LEAST |
| | ONE RECEPTACLE MUST BE ADDED, SEE |
| | REVIEWED SET. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |