2004-06-17 00:00:00BUILDING REVIEW CHECKLIST:
 1-PROVIDE NOTICE OF COMMENCEMENT.
 2-ENGINEER TO HAVE HIS TITLE BLOCK WITH
 ALL HIS INFO. IN ALL DWGS AS REQ'D BY
 CHAPTER 471 FL. ST. INCLUDING FIRM
 REGISTRATION NAME AND NUMBER.
 3-AS PER BUILDING OFFICIAL ZERO LOT LINE
 HOUSES NEED TO HAVE RECORDED EASEMENT
 DEDICATED FOR EGRESS.
 4-GLASS BLOCK AT ZERO LOT LINE NEED TO
 BE ONE HR FIRE RATED ASSEMBLY AS REQ'D
 BY TABLE 600 FBC 2001. DWGS TO SPECIFY
 1HR FIRE RATED GLASS BLOCK ASSEMBLY &
 REVISE DETAIL ON SHEET A-4 TO MATCH
 SUCH ASSEMBLY. SPECIFY UL ASSEMBLY.
 5-PROVIDE ATTIC ACCESS AT GUEST ROOM
 AREA. SEC. 2309.6 FBC 2001
 **SPECIFY ATTIC ACCESS SIZE FOR MAIN
 ROOF. SEC. 2309.6 FBC 2001.
 6-DESIGN CRITERIA NEED TO INCLUDE 30PSF
 OR 10PSF ATTIC LIVE LOAD AS REQUIRED
 BY TABLE 1604.1 FBC 2001.
 7-PROVIDE SOIL TEST REPORT.
 8-PROVIDE DETAIL/SECTION AND SPECS FOR
 CEILING INSTALLATION AT ENTRY AND REAR
 PORCHES. SEE ASTM C-926 & ASTM C-1063
 FOR SPECS, FASTENER SIZES & SPACING.
 9-PROVIDE COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL FOR:
 A)GARAGE DOOR THAT MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER.
 B)WINDOW MULLIONS AND CLEARLY INDICATE
 ON DWGS COMPONENTS TO BE USED.
 C)SINGLE HUNG WINDOWS.
 D)FIXED WINDOWS.
 E)FRENCH DOOR AND PROVIDE ONLY PRODUCT
 APPROVAL FOR DOOR TO BE INSTALLED.
 F)SLIDING GLASS DOORS WITH TRANSOM ABOVE
 SINGLE ASSEMBLY AS SHOWN ON PLANS.
 G)GLASS BLOCK: 1 HR FIRE RATED ASSEMBLY.
 H)ROOF TILE.
 I)STRUCTURAL CONNECTORS.
 J)INSWING ENTRY DOORS WITH TRANSOM ABOVE
 SINGLE ASSEMBLY AS SHOWN ON PLANS.
 10-STORM SHUTTERS PACKAGE: A)PROVIDE KEY
 PLAN & COMPLETE INSTALLATION SCHEDULE.
 B)CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 DESIGN PRESSURES, EDGE DISTANCE, PANEL
 SPAN, CONNECTION TYPE AND STRUCTURE TO
 BE ATTACHED TO (MASONRY OR CONCRETE)
 C)NEED FLORIDA OR LOCAL PRODUCT APPROVAL
 11-TRUSS DRAWINGS PACKAGE: A)ENGINEER TO
 PROVIDE ORIGINAL SIGNATURE, SEAL AND
 DATE AS REQUIRED BY CHAPTER 471 FL. ST
 B)COVER SHEET:*MISSING INFORMATION FOR
 STRUCTURAL ENGINEER OF RECORD.
 **SPECIFY ENCLOSURE CLASSIFICATION.
 C)TRUSS PACKAGE TO BE REVIEWED AND
 APPROVED BY ENGINEER OF RECORD.
 D)CHECK/REVISE HEIGHT OF PLATES. SEE
 STRUCTURAL DWGS FOR CORRECT HEIGHT.
 E)ADDRESS COMENTS TO TRUSS PACKAGE AND
 PROVIDE THIS INFORMATION TO BUILDING
 INSPECTOR FOR ROOF FRAMING INSPECTION.
 12-SHEET A-2: OPENING PRESSURES ARE
 CALCULATED BY PSF NOT PSI. REVISE NOTES
 13-SHEET A-4: A)REVISE WINDOW AND DOOR
 BUCK DETAILS TO COMPLY WITH SECTION
 1707.4.4.2 FBC 2001 TO PROVIDE FULL
 DOOR/WINDOW SUPPORT & NON BEVELED BUCK
 B)DOOR BUCK DETAIL: CLARIFY FASTENER TO
 BE USED. TAPCONS OR HILTI GUN NAILS?
 14-SHEET A-5: A)SEE CHAPTER 19 FBC 2001
 FOR CORRECT ACI SECTION REFERENCED.
 B)ROOF SHEATHING NOTES AND ATTACHMENT/
 FASTENER SPECS TABLE: CLARIFY/REVISE
 TO MATCH INFORMATION GIVEN ON SHEETS
 A2 AND A2.1 STRUCTURAL NOTES.
 15-SHEET S-2: A)REVISE/UPDATE TRUSS
 ANCHOR SCHEDULE TO COMPLY WITH SECTION
 1609.4.3 FBC 2001. SEE 2004 SIMPSON
 CATALOGUE WHICH HAVE REVISED VALUES &
 TYPE AND NUMBER OF FASTENERS TO COMPLY
 WITH THIS SECTION. PROVIDE COMPLETE
 ENGINEERING CALCS FOR TYPE AND NUMBER
 OF FASTENERS DIFFERENT THAN THOSE
 PUBLISHED BY MANUFACTURER. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)PROVIDE BEAM AND LINTEL SCHEUDLE. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 C)CONNECTOR SPECIFIED FOR TRUSSES AT
 ATRIUM AREA DON'T RESIST CALCULATED
 LOADS. SEE ENGINEERED TRUSSES. ALSO,
 BEARING POINTS SHOWN DON'T MATCH THOSE
 DESIGNED ON ENGINEERED TRUSSES. REVISE
 AS REQUIRED. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 D)SHEATHING NOTE TO MATCH SPECS SHOWN ON
 SHEET A-2 AND A-2.1.
 E)WHERE IS SIMPSON HUC610 TAKEN FROM?
 UNABLE TO FIND IT IN 2004 CATALOGUE.
 IS THE THE RIGHT SIZE HANGER FOR (3)
 2X12 BEAM?. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 F)SPECIFY CALCULATED UPLIFT AT THE ENDS
 OF REAR PORCH BEAMS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 G)CONNECTOR SPECIFIED FOR TRUSSES ON TOP
 OF (3)2X12 BEAM IS FOR WOOD TO MASONRY
 CONDITION. NEED WOOD TO WOOD CONNECTOR
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 16-SHEET S-3: A)UPDATE GENERAL NOTES.
 SEE CHAPTER 19 AND 35 FOR SPECIFIC
 REFERENCE STANDARDS AND EDITION USED
 FOR CONCRETE CONSTRUCTION.
 B)BUCK DETAIL DOESN'T MATCH BUCK DETAILS
 ON SHEET A-4. NEED ONLY ONE DETAIL TO
 AVOID CONFLICTS. REVISE DETAIL TO
 COMPLY WITH SEC. 1707.4.4.2 FBC 2001.
 SHOW FULL DOOR/WINDOW SUPPORT AND NO
 BEVELED EDGE.
 C)REVISE TYP. FOOTING SECTION. NEED 1.5"
 WATER RECESS. SEC. 2111.1.9 CITY
 AMENDMENTS TO FBC 2001.
 D)REVISE ROOF SHEATHING SPECS ON DETAIL
 2-S3 TO MATCH SPECS ON SHEET A-2/A-2.1
  
 17-REVISE ALL GENERAL NOTES WHERE IT
 SAYS "ARCHITECT". THIS PLANS WERE
 PREPARED BY AN ENGINEER, NOT ARCHITECT
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.