| 2006-03-17 00:00:00 | *********** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SEE SEC'S AND FEEDERS |
| | AHVE NOW BEEN DECREASED WHICH ARE NOT |
| | RATED FOR THE OCP AS SHOWNA OR THE SIZE |
| | OF SERVICE. ORIG PLANS INDICATED A 200A |
| | SERVICE, THEN THE REVISED PLANS IN JAN |
| | 05 INDICATED A 225A SERVICE WHICH THE |
| | SEC'S AND FEEDER WERE INCREASED. |
| | PLEASE SEE 310.16 FOR COMMERCIAL USE |
| | WHICH REQUIRES THESE CONDUCTORS TO BE |
| | INCREASED. |
| | 310.16,240.4, ETC |
| | |
| | 2) NOTE: DUE TO THE INCREASEOF SERVICE |
| | ENTRANCE CONDUCTORS, THE PLANS WERE |
| | REDLINED ON JAN 24,2005 TO INCREASE THE |
| | GROUNDING ELECTRODE CONDUCTOR. THISWAS |
| | NOT DONE AND STILL SHOWS A GROUNDING |
| | ELECTRODE TOO SMALL. |
| | #2 MIN).250.66, 250.50,250.52 |
| | |
| | 3)NOTE: PLEASE COMPLETE ALL CIRCUTING ON |
| | PLANS AND CORRELATE W/ THE SUBMITTED |
| | PANEL SCHEDULE. |
| | PLEASE SEE 700.12E FOR EM/EXT. |
| | |
| | 4)NOTE: PLEASEBE SURE TO GO OVER PLANS |
| | AND MAKE SURE ALL CIRCUITS CORRELATE. |
| | PLEASE SEE RECEPT IN BATH ON LT CIRCUIT. |
| | PLEASE SEE RECEPT ON LT CIRCUIT ON A |
| | DIFFERENT FLR. |
| | |
| | MOST OF THE ABOVE AREAS HAVEBEEN |
| | REDLINED, HOWEVER THIS IN NO WAY |
| | INCLUDES ALL. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |