| 2004-06-05 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | |
| | |
| | 1) SHT 1 OF 5 GROUND FLOOR PLAN. LOUNGE |
| | SINK SHALL COMPLY WITH 11-4.24 AND ALL |
| | SUBSECTIONS. SHOW TURNING AREA SEE FIGS |
| | 3A & 3B. SECTION 11-4.2.3 & 11-4.2.4.2 |
| | 2) SHT 1 OF 5 GROUND FLOOR PLAN. TOILET |
| | ROOM - SHOW CLEAR FLOOR SPACE FOR LAV & |
| | W/C. SHOW TURNING AREA PER SECTION 11-4. |
| | 22.3. |
| | 3) SHT 1 OF 5 DOORS SHALL NOT SWING INTO |
| | THE CLEAR FLOOR SPACE FOR ANY FIXTURE. |
| | SEE TOILET ROOM DOOR. SECTION 11-4.22.2 |
| | 4) PER TABLE 403.1 A DRINKING FOUNTAIN |
| | IS REQUIRED. ALSO SEE SECTION 410.1. |
| | 5) SHOW LOCATION OF WATER HEATER ON THE |
| | FLOOR PLAN. SECTION 104.2.1 |
| | 6) SUBMIT A WATER RISER DIAGRAM. SECTION |
| | 104.3.1.1 - SHOW LOCATION OF WATER HAMM- |
| | ER ARRESTORS PER PDI-WH 201. |
| | 7) SHT 5 OF 5 UNDER PLUMBING NOTES THERE |
| | ARE GAS NOTES. A SEPARATE GAS PERMIT IS |
| | REQUIRED IF THERE IS GAS BEING INSTALLED |
| | SEPARATE GAS PLANS REQUIRED ALSO. SECT- |
| | ION 104.3.1.1 |
| | 8) SEE ELECTRICAL REVIEW CONCERNING THE |
| | SIGNATURE OF THE ARCHITECT, AND REMOVAL |
| | OF OLD SHEETS WHEN RESUBMITTING PLANS. |
| | |