| Plan Review Notes For Permit 04050860 |
| Permit Number |
04050860 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-08 00:00:00 | DENIED: | | | 1.PLAN SHEET 5 OF 5 NOTE #17, OUTSIDE | | | AIR CALCS BASED ON ASHRAE 62-89.PLEASE | | | PROVIDE THE CALCULATIONS. | | | | | | 2.INDICATE OUTSIDE AIR DUCT, SIZE, | | | MATERIAL, LAYOUT & INTAKE LOCATION. | | | | | | 3.THE GROUND FLOOR MECHANICAL PLAN | | | SOME OF THE DUCTS ARE NOT SIZED. | | | | | | 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | IN NORMALLY OCCUUPIED AREAS PER NFPA 90A | | | 6.4.4.3 (1). | | | | | | 5.DETAIL FOR THE REFRIGERANT LINES | | | DOES NOT INDICATE INSULATION ON THE | | | PIPING PER 2001 FBC CHAPTER 13 SUB- | | | CHAPTER 611.1.ABC.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|