| 2004-05-28 00:00:00 | ************* UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SEE BLDG IS SHOWN AS A |
| | CHANGE OF OCCUPANCY FROM RESIDENCE TO |
| | COMMERCIAL OFFICE BLDG. |
| | PLEASE ADJUST PLANS ACCORD. |
| | |
| | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. |
| | |
| | 3)NOTE: PLEASE SEE NEC 220 FOR LOAD |
| | PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | |
| | 4)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- |
| | -ING OF EM/ EXT LTS. |
| | PLEASE SEE FIRE REVIEW COMMENTS FOR |
| | EM/EXT LTS. |
| | |
| | 5)NOTE: PLEASE SEE OCP SHOWN FOR AHU'S |
| | DO NOT SEEM TO CORRELATE TO NEC 424.3B |
| | PLEASE VERIFY KW LOAD AND OCP. |
| | |
| | 6)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAIN TO PANEL. |
| | 250.110,250.122,250.24 |
| | |
| | 7)NOTE: PLEASE CORRELATE RISER WITH |
| | PANEL, ONE SHOWS PANEL BEING MCB, OTHER |
| | SHOWS MLO?? |
| | |
| | 8)NOTE: PLEASE SEE SEC'S SHOWN AS 1/0'S |
| | PLEASE SEE 310.16 FOR MIN SEC'S FOR A |
| | 200A SERVICE. |
| | |
| | 9)NOTE: PLEASE SEE 210.70/210.63 FOR |
| | AHU WHICH APPEARS TO BE IN AN ATTIC?? |
| | |
| | 10)NOTE: PLEASE SEE FS 481.221 WHICH |
| | REQUIRES A SIGNATURE FOR ARCH. |
| | PLEASE SEE THAT PLANS APPEAR TO AN |
| | INITIAL FOR FIRST NAME. |
| | IF THIS IS LEGAL "SIGNATURE", PLEASE |
| | PROVIDE A SIGNED, DATED AND SEALED |
| | NOTARIZED LETTER STATING THIS IS LEGAL |
| | SIGNATURE. WE CAN THEN PLACE THIS IN |
| | A SIGNATURE FILE FOR FUTURE REFERENCE |
| | DUE TO ISSUES WE HAVE ENCOUNTERED WITH |
| | MORE THAN ONE "SIGNATURE" FOR INDIVIDUAL |
| | 'S ON PLANS BEING SUBMITTED TO CITY OF |
| | WEST PALM BEACH. WE ARE REQUIRING |
| | "SIGNATURE" VERIFICATION FOR FILE. |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | INCLUDING IMPACT FEES FOR PALM BEACH |
| | COUNTY. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO SETS FOR |
| | REVIEW AND STAMPING. ONE SET OF OLD |
| | SHEETS MAY BE SUBMITTED FOR REFERENCE |
| | FOR SOME REVIEWS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |