| 2004-06-09 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)THE NOTICE OF COMMENCEMENT IS |
| | EXPIRED (OVER 90 DAYS WITHOUT |
| | COMMENCING WORK), FS713.13. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY (CHANGE OF USE).THE |
| | PLANS MUST BE STAMPED AND THE RECEIPT |
| | ATTACHED TO THE APPLICATION.233-5025 |
| | |
| | 3.)PROVIDE A COPY OF THE SURVEY FOR |
| | THIS PROPERTY. |
| | |
| | 4.)SEPARATE PERMITS REQUIRED. |
| | |
| | 5.)RENOVATED BUILDINGS ARE REQUIRED |
| | TO COMPLY WITH FBC12-101.1.3, FORM |
| | 400D OR WITH METHOD B SUBCHAPTER 4. |
| | |
| | 6.)PROVIDE TEST REPORTS AND FLORIDA |
| | STATEWIDE, LOCAL OR SITE SPECIFIC |
| | PRODUCT APPROVALS FOR THE FOLLOWING: |
| | FIXED GLASS WINDOW |
| | SINGLE HUNG WINDOW |
| | IMPACT PROTECTION |
| | DOOR |
| | ROOF |
| | ANY OTHER PRODUCT APPROVALS AS REQUIRED. |
| | |
| | 7.)SHEET 2, WIND DESIGN INFORMATION |
| | INDICATES A HEIGHT OF 15' WHICH |
| | CONFLICTS WITH THE PLAN. |
| | |
| | 8.)11-4.8.4.(2) LANDINGS. ALL LANDINGS |
| | ON RAMPS SHALL NOT BE LESS THAN 60" |
| | CLEAR, & THE BOTTOM OF EACH RAMP SHALL |
| | HAVE NOT LESS THAN 72" OF STRAIGHT & |
| | LEVEL CLEARANCE. |
| | |
| | 9.)11-4.8.4(3) IF RAMPS CHANGE DIREC- |
| | TION AT LANDINGS, THE MINIMUM LANDING |
| | SIZE SHALL BE 60" X 60". |
| | |
| | 10.) THE FIRST FLOOR TOILET DOOR |
| | ENCROACHES UPON THE CLEAR FLOOR SPACE |
| | REQUIRED BY FBC11-4.19.3, FBC11-4.23.2. |
| | THIS DOOR US TO COMPLY WITH FBC1012.1.4. |
| | SHOW THE REQUIRED FLOOR SPACE, TO SCALE, |
| | ON THE FLOOR PLAN. |
| | |
| | 11.)THE 2ND FLOOR TOILET DOOR DOES NOT |
| | COMPLY WITH FBC1012.1.4. |
| | |
| | 12.)IT APPEARS THAT THE NEW STAIRS |
| | IS THE MAIN EGRESS FOR THE 2ND FLOOR. |
| | THIS STAIR IS TO COMPLY WITH FBC1006. |
| | 2.4.SHOW HOW THIS 1 HR PROTECTION IS |
| | OBTAINED.INDICATE ALL OPENINGS |
| | REQUIRED TO BE PROTECTED ON THE PLAN. |
| | |
| | 13.)FBC1006.1.4, THERE IS TO BE NO |
| | USABLE SPACE UNDER THE STAIR UNLESS |
| | PROTECTED BY THE SAME FIRE RESISTANCE AS |
| | THE EXIT ENCLOSURE (MIN. 1 HR). |
| | |
| | 14.)THE LOUNGE DOOR LACKS THE |
| | MANUEVERING CLEARANCE REQUIRED BY |
| | FBC11-4.13-6 AND FBC 11-FIGURE 25(A). |
| | |
| | 15.)THE LOUNGE SINK IS TO COMPLY WITH |
| | FBC11-4.24. |
| | |
| | 16.)PROVIDE AN AFFIDAVIT CERTIFYING |
| | THE FLOOR LOADING, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO THE FBC104.3.2, |
| | FBC TABLE 1604.1. |
| | |
| | 17.)THE EXTERIOR STAIR RAILING SERVES |
| | AS A GUARDRAIL AS WELL AS A HANDRAIL, |
| | TO COMPLY WITH FBC1608.2.2, FBC1608.2.1, |
| | FBC1007.5, FBC1015.ALL HANDRAILS TO |
| | COMPLY WITH FBC1608.2.1. |
| | |
| | 18.)EDGE PROTECTION REQUIRED FOR THE |
| | RAMP, FBC1013.8. |
| | |
| | 19.)HANDRAILS REQUIRED ON BOTH SIDES |
| | OF THE STAIRS, FBC1007.5.2. |
| | |
| | 20.)PROVIDE A SOILS INVESTIGATION |
| | REPORT. |
| | |
| | 21.)HANDRAIL FOR THE STAIRS ARE TO |
| | COMPLY WITH FBC11-4.9.4(2), FBC FIGURE |
| | 19(C). |
| | |
| | 22.)CRAWL SPACE IS TO COMPLY WITH |
| | FBC1804.6.1 |
| | |
| | 22.)WHEN RESUBMITTING, PLEASE SUBMIT |
| | A TRANSMITTAL LETTER EXPLAINING HOW |
| | EACH ITEM WAS ADDRESSED. |