Plan Review Notes
Plan Review Notes For Permit 04050856
Permit Number 04050856
Review Stop M
Sequence Number 1
Notes
Date Text
2004-06-09 00:00:00DENIED:
 1.CERTIFICATE OF AUTHORIZATION # ON
 THE TITLE BLOCK IS NOT CORRECT ACCORDING
 TO DBPR.PLEASE CORRECT.
  
 2.PLANS DO NOT INDICATE PIPING
 MATERIAL FOR THE CONDENSATE.NO
 COMBUSTIBLES ALLOWED ABOVE THE CEILING
 IN THE RETURN AIR PLENUM AS NOTED ON
 PLAN SHEET M1.0 OR M2.0.
  
 3.PLANS DO NOT INDICATE OUTSIDE AIR
 FOR THE NEW FCU-2.PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.