| Plan Review Notes For Permit 04050820 |
| Permit Number |
04050820 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-05-24 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE PROVIDE A CALCULATION | | | INCLUDING ALL ADDED LOADS IMPOSED,ALL | | | EXISTING LOADS AND THE EXISTING OR | | | PROPOSED SERVICE SPECIFICATIONS PER | | | 215.15. | | | | | | 2} PLEASE ADD A RECEPTACLE AT THE REAR | | | OF THE HOUSE TO COMPLY WITH 210.52(E). | | | | | | 3} PLEASE NOTE THAT THE ARCHITECTS | | | SIGNATURE IS REQUIRED ON HIS/HER SEAL | | | PER 61G1-16.003. INITIALS ARE NOT | | | ACCEPTABLE. ALSO NOTE THE FIRMS LICENSE | | | NUMBER IS REQIRED IN THE TITLE BLOCK IN | | | THE TITLE BLOCK PER 61G1-16.004. | | | | | | 4} RECEPTALES ARE MISSING IN THE KITCHEN | | | ON THE COUNTERTOP AND THE PENINSULAR PER | | | 215.52(C)(1) & (4). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|