Plan Review Notes
Plan Review Notes For Permit 04050820
Permit Number 04050820
Review Stop E
Sequence Number 1
Notes
Date Text
2004-05-24 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED SERVICE SPECIFICATIONS PER
 215.15.
  
 2} PLEASE ADD A RECEPTACLE AT THE REAR
 OF THE HOUSE TO COMPLY WITH 210.52(E).
  
 3} PLEASE NOTE THAT THE ARCHITECTS
 SIGNATURE IS REQUIRED ON HIS/HER SEAL
 PER 61G1-16.003. INITIALS ARE NOT
 ACCEPTABLE. ALSO NOTE THE FIRMS LICENSE
 NUMBER IS REQIRED IN THE TITLE BLOCK IN
 THE TITLE BLOCK PER 61G1-16.004.
  
 4} RECEPTALES ARE MISSING IN THE KITCHEN
 ON THE COUNTERTOP AND THE PENINSULAR PER
 215.52(C)(1) & (4).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW