Plan Review Notes
Plan Review Notes For Permit 04050773
Permit Number 04050773
Review Stop P
Sequence Number 1
Notes
Date Text
2004-06-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT 1 DEMO NOTES #4 & #5 - NO DEAD
 ENDS ALLOWED IN THE REMOVAL OF ANY PART
 OF THE DRAINAGE SYSTEM. SECTION 704.5
 2) SHT 3 GENERAL PLUMBING NOTES #17, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 REFERENCE NOTE. SECTION 604.9
 3) SHT 3 WATER HEATER SHALL BE ACCESSIB-
 LE. SUBMIT A DETAIL. - SUBMIT A DETAIL
 FOR THE PIPING OF THE T/P RELEIF VALVE
 DISCHARGE AND THE EMERGENCY HEATER PAN
 DRAINAGE PIPING. SECTIONS 501.4 AND
 104.2.1
 4) SHT 3 THERMAL EXPANSION CONTROL IS
 REQUIRED FOR THE WATER HEATER. SECTION
 607.3.2.
 5) A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. (ALSO SEE SECTION 410.1)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]