| Plan Review Notes For Permit 04050773 |
| Permit Number |
04050773 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT 1 DEMO NOTES #4 & #5 - NO DEAD | | | ENDS ALLOWED IN THE REMOVAL OF ANY PART | | | OF THE DRAINAGE SYSTEM. SECTION 704.5 | | | 2) SHT 3 GENERAL PLUMBING NOTES #17, AIR | | | CHAMBERS ARE NOT APPROVED. DELETE FROM | | | REFERENCE NOTE. SECTION 604.9 | | | 3) SHT 3 WATER HEATER SHALL BE ACCESSIB- | | | LE. SUBMIT A DETAIL. - SUBMIT A DETAIL | | | FOR THE PIPING OF THE T/P RELEIF VALVE | | | DISCHARGE AND THE EMERGENCY HEATER PAN | | | DRAINAGE PIPING. SECTIONS 501.4 AND | | | 104.2.1 | | | 4) SHT 3 THERMAL EXPANSION CONTROL IS | | | REQUIRED FOR THE WATER HEATER. SECTION | | | 607.3.2. | | | 5) A DRINKING FOUNTAIN IS REQUIRED PER | | | TABLE 403.1. (ALSO SEE SECTION 410.1) | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|