| Plan Review Notes For Permit 04050773 |
| Permit Number |
04050773 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-17 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)THE DOCTOR'S TOILET SHALL BE | | | ADAPTABLE FBC11-4.1.3(11) (GRAB BAR | | | BACKING, SINK), PROVIDE A DETAIL. CLEAR | | | FLOOR SPACE REQUIRED FBC11-4.23.3. | | | | | | 3.)SHOW CLEAR FLOOR SPACE FOR | | | FIXTURES. | | | | | | 4.)DOORS SHALL NOT SWING INTO THE | | | FLOOR SPACE REQUIRED FOR ANY FIXTURE | | | FBC11-4.23.2 (HANDICAP TOILET). | | | | | | 5.)RE: THE NEW CASED OPENINGS, PROVIDE | | | INFORMATION ABOUT THE WALL, IS A HEADER | | | REQUIRED? | | | | | | 6.)THE GRAB BAR AT THE WATER CLOSET IS | | | TO BE 36" MIN, FBC 11-FIGURE 29. | | | | | | 7.) 1503.4.4 PROTECTION AGAINST DECAY & | | | TERMITES. CONDENSATE LINES & ROOF DOWN | | | SPOUTS SHALL DISCHARGE AT LEAST 1 FT. | | | AWAY FROM THE STRUCTURE SIDEWALL, | | | WHETHER BY UNDERGROUND PIPING, TAIL EX- | | | TENSIONS, OR SPLASH BLOCKS. |
|