| Plan Review Notes For Permit 04050770 |
| Permit Number |
04050770 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-09-21 00:00:00 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTPER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SHTS A-13 & A-14 FLOOR DRAINS ARE NOT | | | AN APPROVED INDIRECT WASTE RECEPTOR. | | | SECTIONS 802.3 & 802.3.2. A FLOOR SINK | | | OR A HUB DRAIN IS REQUIRED FOR INDIRECT | | | WASTE. | | | 2. SHTS A-13 & A-14 THE PERSONAL | | | SIGNATURE IS REQUIRED ON THE SEAL PER | | | FAC 61G1-16.003 & FAC 61G1-16.004(5). | | | INITIALS ARE NOT APPROVED. FS 481.2055. | | | 3. SHT A-13 FLOOR DRAIN IN TOILET ROOM | | | IS NOT VENTED AS SHOWN. SEE RED LINE | | | CORRECTION ON PLANS FOR THE CORRECT | | | CONNECTION OF W/C TO BUILDING DRAIN. | | | THIS WAS RED LINED ON ISSUED SET OF | | | PLANS AND SHALL BE CORRECTED ON | | | REVISION. SECTIONS 901.2.1 & 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|