2005-09-21 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTPER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS A-13 & A-14 FLOOR DRAINS ARE NOT
 AN APPROVED INDIRECT WASTE RECEPTOR.
 SECTIONS 802.3 & 802.3.2. A FLOOR SINK
 OR A HUB DRAIN IS REQUIRED FOR INDIRECT
 WASTE.
 2. SHTS A-13 & A-14 THE PERSONAL
 SIGNATURE IS REQUIRED ON THE SEAL PER
 FAC 61G1-16.003 & FAC 61G1-16.004(5).
 INITIALS ARE NOT APPROVED. FS 481.2055.
 3. SHT A-13 FLOOR DRAIN IN TOILET ROOM
 IS NOT VENTED AS SHOWN. SEE RED LINE
 CORRECTION ON PLANS FOR THE CORRECT
 CONNECTION OF W/C TO BUILDING DRAIN.
 THIS WAS RED LINED ON ISSUED SET OF
 PLANS AND SHALL BE CORRECTED ON
 REVISION. SECTIONS 901.2.1 & 104.2.1.
  