Plan Review Notes
Plan Review Notes For Permit 04050770
Permit Number 04050770
Review Stop B
Sequence Number 4
Notes
Date Text
2004-10-27 00:00:00BUILDING PLAN REVIEW
 PERMIT:04050770
 ADD:2175 PALM BEACH LAKES BLVD
 CONT:TAYCON CONST. MANAGEMENT INC.
 TEL: (561)622-2699
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 4THREVIEW
 ACTION:DENIED
  
  
 1) FL. BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PLEASE PROVIDE TWO COPIES
 (3COPIES IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PROCUCT TESTING REPORTS,
 MISSING REPORTS ARE AS FOLLOWS.
 A) WINDOWS: PLEASE HAVE THE APPLICATION
 PROVIDED COMPLETE BY THE MANUFACTURE
 FOR THE WINDOWS SUBMITTED. IF NOT, YOU
 MAY SUBMIT A STATE APPROVE WINDOW
 PRODUCT.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
 YOU CAN ASK IF THERE IS ANY CREDIT FROM
 THE PREVIOUS BUILDING WHICH WAS DEMO.
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEW
 TEL: (561) 805-6726
 FAX: (561) 659-8026