| Plan Review Notes For Permit 04050770 |
| Permit Number |
04050770 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-08-21 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHTS A-1 & A-2, SHT A-1 SHOWS A PRO- | | | POSED 750 GAL SAND/OIL INTERCEPTOR, | | | WHEREAS SHT A-2 SHOWS A 158 GAL INTECEP- | | | TOR. PLEASE CORRELATE PLANS/DETAILS. | | | SECTION 104.2.1 | | | 2) FROM PREVIOUS REVIEW: ROUTE PLANS TO | | | DBPR HOTEL AND RESTURANT DIVISION. RES- | | | PONSE NOTED BUT UNABLE TO FIND INFORMAT- | | | ION FROM RESPONSE. PLEASE CLARIFY. SECT- | | | ION 104.2.1 | | | 3) FROM PREVIOUS REVIEW: SHT A-3 WATER | | | FILTERS SHALL COMPLY WITH NSF-42. MANUF. | | | INFORMATION IS NOT CLEAR AND HARD TO | | | READ, AND DOES NOT INDICATE COMPLIANCE | | | WITH NSF-42. PLEASE SUBMIT MANUF. INFOR- | | | MATION SHOWING THAT FILTERS COMPLY WITH | | | NSF-42. SECTION 611.1 | | | 4) FROM PREVIOUS REVIEW: SUBMIT PLANS | | | FOR CAR WASH. NO RESPONSE NOTED. SECTION | | | 1-4.2.1 & 104.3.1.1 | | | 5) SHT A-1 REFERS TO CIVIL PLANS. CIVIL | | | PLANS ARE NOT SUBMITTED. PLEASE SUBMIT | | | A SET OF CIVIL PLANS TO CORRELATE INFOR- | | | MATION REQUIRED TO APPROVE PLANS. SECT- | | | ION 104.2.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|