2004-08-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHTS A-1 & A-2, SHT A-1 SHOWS A PRO-
 POSED 750 GAL SAND/OIL INTERCEPTOR,
 WHEREAS SHT A-2 SHOWS A 158 GAL INTECEP-
 TOR. PLEASE CORRELATE PLANS/DETAILS.
 SECTION 104.2.1
 2) FROM PREVIOUS REVIEW: ROUTE PLANS TO
 DBPR HOTEL AND RESTURANT DIVISION. RES-
 PONSE NOTED BUT UNABLE TO FIND INFORMAT-
 ION FROM RESPONSE. PLEASE CLARIFY. SECT-
 ION 104.2.1
 3) FROM PREVIOUS REVIEW: SHT A-3 WATER
 FILTERS SHALL COMPLY WITH NSF-42. MANUF.
 INFORMATION IS NOT CLEAR AND HARD TO
 READ, AND DOES NOT INDICATE COMPLIANCE
 WITH NSF-42. PLEASE SUBMIT MANUF. INFOR-
 MATION SHOWING THAT FILTERS COMPLY WITH
 NSF-42. SECTION 611.1
 4) FROM PREVIOUS REVIEW: SUBMIT PLANS
 FOR CAR WASH. NO RESPONSE NOTED. SECTION
 1-4.2.1 & 104.3.1.1
 5) SHT A-1 REFERS TO CIVIL PLANS. CIVIL
 PLANS ARE NOT SUBMITTED. PLEASE SUBMIT
 A SET OF CIVIL PLANS TO CORRELATE INFOR-
 MATION REQUIRED TO APPROVE PLANS. SECT-
 ION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]