Plan Review Notes
Plan Review Notes For Permit 04050770
Permit Number 04050770
Review Stop E
Sequence Number 2
Notes
Date Text
2004-08-16 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE SEE PANEL "B" IS STILL
 SHOWN W/ 20A OCP AND #12 TO A PANEL
 SHOWN WITH A 71A LOAD??
 PLEASE SEE THIS WAS ON ORIGINAL NOTES.
  
 2)NOTE: PLEASE SEE RISER DIAGRAM INDICAT
 -ES EQUIPMENT GROUNDING CONDUCTORS
 INSTALLED BEFORE AND AFTER FIRST MEANS
 OF DISCONNETC. EQUIPMENT GRNDS ARE ONLY
 PERMITTED AFTER THE FIRST MEANS OF DISC.
 250.6,250.24
 PLEASE ADJUST RISER.
  
 3)NOTE: PLEASE SEE A-17 WHICH CONTAINS
 A TITLE BLOCK FOR "COBURN & ASSC INC".
 PLEASE SEE THE ELECTRICAL PLANS DO NOT
 CONTAIN THIS SAME TITLE BLOCK FROM
 CONBURN & ASSC? FS 553.79 PE REQUIRED.
 PLEASE ALSO SEE FAC 61G15-23.002, WHICH
 ALSO REQUIRES TO HAVE THE PRINTED NAME
 AND LICENSE #(PE) INCLUDED IN TITLE
 BLOCK.
  
 4)NOTE: PLEASE SEE RISER INDICATES A
 PANEL CW AND NO PANEL SCHEDULE WAS
 SUBMITTED.?
  
 5 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 LOAD SHOWN APPEARS TO BE CONNECTED LOAD?
  
 PLEASE SEE POSSILE COMMENTS FROM OTHER
 REVIEWERS THAT MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]