| 2004-08-16 00:00:00 | *********** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE PANEL "B" IS STILL |
| | SHOWN W/ 20A OCP AND #12 TO A PANEL |
| | SHOWN WITH A 71A LOAD?? |
| | PLEASE SEE THIS WAS ON ORIGINAL NOTES. |
| | |
| | 2)NOTE: PLEASE SEE RISER DIAGRAM INDICAT |
| | -ES EQUIPMENT GROUNDING CONDUCTORS |
| | INSTALLED BEFORE AND AFTER FIRST MEANS |
| | OF DISCONNETC. EQUIPMENT GRNDS ARE ONLY |
| | PERMITTED AFTER THE FIRST MEANS OF DISC. |
| | 250.6,250.24 |
| | PLEASE ADJUST RISER. |
| | |
| | 3)NOTE: PLEASE SEE A-17 WHICH CONTAINS |
| | A TITLE BLOCK FOR "COBURN & ASSC INC". |
| | PLEASE SEE THE ELECTRICAL PLANS DO NOT |
| | CONTAIN THIS SAME TITLE BLOCK FROM |
| | CONBURN & ASSC? FS 553.79 PE REQUIRED. |
| | PLEASE ALSO SEE FAC 61G15-23.002, WHICH |
| | ALSO REQUIRES TO HAVE THE PRINTED NAME |
| | AND LICENSE #(PE) INCLUDED IN TITLE |
| | BLOCK. |
| | |
| | 4)NOTE: PLEASE SEE RISER INDICATES A |
| | PANEL CW AND NO PANEL SCHEDULE WAS |
| | SUBMITTED.? |
| | |
| | 5 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | LOAD SHOWN APPEARS TO BE CONNECTED LOAD? |
| | |
| | PLEASE SEE POSSILE COMMENTS FROM OTHER |
| | REVIEWERS THAT MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |