| Date |
Text |
| 2004-06-05 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1) CONTACT RODNEY COMPO, ENVIRONMENTAL |
| | MANAGER FOR SIZING OF GREASE INTERCEPTOR |
| | AND OIL/SAND INTERCEPTOR. WASET ORDINAN- |
| | CE 2938-96. (561) 837-4074. |
| | 2) ROUTE PLANS TO DBPR HOTEL AND RESTUR- |
| | AND DIVISION FOR REVIEW PRIOR TO RESUB- |
| | MITTING FOR REVIEW AT CITY WPB. PLANS |
| | SHALL BE STAMPED AND WORKSHEETS ATTACHED |
| | TO EACH SET OF PLANS FOR REVIEW. SECTION |
| | 101.4.7 |
| | 3) SHT A-3 SHOW CLEAR FLOOR SPACE FOR |
| | FIXTURES IN WOMENS TOILET ROOM. SECTIONS |
| | 11-4.16.2 AND 11-4.19.3. |
| | 4) SHT A-3 WATER FILTERS SHALL COMPLY |
| | WITH NSF-42. SUBMIT MANUF. SPECIFICATION |
| | SHEETS. SECTION 611.1 |
| | 5) SEPARATE PERMITS ARE REQUIRED FOR: |
| | - GREASE INTERCEPTORS |
| | - OIL/SAND INTERCEPTORS |
| | - IRRIGATION |
| | - CAR WASH SYSTEM - SUBMIT PLANS. |
| | 6) SHT A-13 THE CODE IN EFFECT IS FBC- |
| | 2001 PLUMBING. PLUMBING NOTES REFERES |
| | TO STANDARD CODE. PLEASE CHANGE REFEREN- |
| | CE. SECTION 104.2.1 |
| | 7) RPZ BACKFLOW IS REQUIRED FOR WATER |
| | SERVICE TO THE CAR WASH. SEC 608.13.2 |
| | 8) SHT A-14 SANITARY RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN (FLAT LAYOUT |
| | ON SHT A-13) NOR DOES IT MEET CODE REQ- |
| | UIREMENTS. |
| | A) A-13 SHOWS ALL FLOOR SINKS ON THE |
| | GREASE LINE. - RISER SHOWS SOME F.S. ON |
| | THE SANT. LINE. |
| | B) A FLOOR DRAIN AND A FLOOR SINK ARE |
| | MISSING ON THE RISER DIAGRAM. |
| | C) THERE IS A HORIZONTAL DRY VENT AFTER |
| | THE LAST FLOOR SINK ON THE GREASE LINE. |
| | THIS FLOOR SINK SHOULD BE CONNECTED ON |
| | THE VERTICAL RISE OF THE VENT. SECTION |
| | 905.3 |
| | D) FLOOR DRAIN IN MENS TOILET ROOM IS |
| | LABLED AS A FLOOR SINK ON THE RISER DIA- |
| | GRAM. |
| | E) LAV ARMS AND TRAP ARE NOT SHOWN ON |
| | THE RISER DIAGRAM. |
| | F) HAND SINK VENT IS SHOWN AS A 3" ON |
| | A-13 AND 2" ON THE RISER DIAGRAM. |
| | PLEASE CORRELATE PLANS. SECTION 104.2.1 |
| | 9) THE PERSONAL SIGNATURE OF THE ARCHIT- |
| | ECT SHALL APPEAR ON ALL ARCHITECTURAL |
| | DOCUMENTS TO BE FILED FOR PUBLIC RECORD. |
| | DOCUMENTS SHALL BE SIGNED PERSONALLY AND |
| | SEALED/DATED BY THE RESPONSIBLE ARCHITE- |
| | CT. INITIALS ARE NOT APPROVED. IF THISIS |
| | YOUR LEGAL SIGNATURE, A COPY OF DRIVERS |
| | LICENSE, VOTERS REGISTRATION, OR ARCHIT- |
| | ECTS LICENSE SHOWING LEGAL SIGNATURE |
| | WITH A NOTARIZED LETTER STATING THAT IS |
| | YOUR LEGAL SIGNATURE FOR OUR FILE WILL |
| | SUFFICE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |