| 2004-06-08 00:00:00 | DENIED: |
| | 1.ENERGY CALCULATIONS INDICATE MAXIMUM |
| | TONNAGE AS 6 TONS.PLAN SHEET A-15 |
| | THE EQUIPMENT SCHEDULE INDICATES A TOTAL |
| | OF 11 TONS. |
| | |
| | 2.ADDITIONAL PERMIT REQUIRED FOR THE |
| | WALK-IN COOLER/FREEZERS.PROVIDE |
| | MANUFACTURER SUBMITTAL DATA WITH PERMIT |
| | APPLICATION. |
| | |
| | 3.PLAN SHEET A-6 INDICATES THE TOP OF |
| | THE JOISTS AS 16' 4".PER 2001 FBC(M) |
| | 306.5, EQUIPMENT LOCATED ON ROOFS AT A |
| | HEIGHT GREATER THAN 16' SHALL HAVE A |
| | PERMANENT MEANS OF ACCESS.SUCH ACCESS |
| | SHALL NOT REQUIRE CLIMBING OVER OBJECTS |
| | GREATER THAN 30". |
| | |
| | 4.PLAN SHEET A-8A, DETAIL FOR THE |
| | CONDENSING UNIT.HEIGHT REQUIREMENT FOR |
| | THE C.U. STAND SHALL COMPLY WITH 2001 |
| | FBC 1511.7 (SEE ATTACHED SCHEDULE). |
| | |
| | 5.INDICATE TERMINATION OF THE |
| | CONDENSATE. |
| | |
| | 6.ADDITIONAL PERMIT REQUIRED FOR THE |
| | UNDERGROUND FUEL TANKS, PLANS TO HAVE |
| | PRIOR APPROVAL FROM PALM BEACH COUNTY |
| | DERM AT 3323 BELVEDERE RD BUILD #502. |
| | ATTENTION CHIP GREEN. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561) 805-6719. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561) 805-6719. |