Plan Review Notes
Plan Review Notes For Permit 04050770
Permit Number 04050770
Review Stop M
Sequence Number 1
Notes
Date Text
2004-06-08 00:00:00DENIED:
 1.ENERGY CALCULATIONS INDICATE MAXIMUM
 TONNAGE AS 6 TONS.PLAN SHEET A-15
 THE EQUIPMENT SCHEDULE INDICATES A TOTAL
 OF 11 TONS.
  
 2.ADDITIONAL PERMIT REQUIRED FOR THE
 WALK-IN COOLER/FREEZERS.PROVIDE
 MANUFACTURER SUBMITTAL DATA WITH PERMIT
 APPLICATION.
  
 3.PLAN SHEET A-6 INDICATES THE TOP OF
 THE JOISTS AS 16' 4".PER 2001 FBC(M)
 306.5, EQUIPMENT LOCATED ON ROOFS AT A
 HEIGHT GREATER THAN 16' SHALL HAVE A
 PERMANENT MEANS OF ACCESS.SUCH ACCESS
 SHALL NOT REQUIRE CLIMBING OVER OBJECTS
 GREATER THAN 30".
  
 4.PLAN SHEET A-8A, DETAIL FOR THE
 CONDENSING UNIT.HEIGHT REQUIREMENT FOR
 THE C.U. STAND SHALL COMPLY WITH 2001
 FBC 1511.7 (SEE ATTACHED SCHEDULE).
  
 5.INDICATE TERMINATION OF THE
 CONDENSATE.
  
 6.ADDITIONAL PERMIT REQUIRED FOR THE
 UNDERGROUND FUEL TANKS, PLANS TO HAVE
 PRIOR APPROVAL FROM PALM BEACH COUNTY
 DERM AT 3323 BELVEDERE RD BUILD #502.
 ATTENTION CHIP GREEN.
  