Plan Review Notes
Plan Review Notes For Permit 04050770
Permit Number 04050770
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-05-25 00:00:001) ALL DEMOLITION, RENOVATION AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
 3) THE PLANS INDICATE TYPE VI
 CONSTRUCTION. TYPE VI CONSTRUCTION IS
 NOT ALLOWED IN THE CITY FIRE LIMITS.
 PLEASE SEE APPENDIX F, LOCAL AMENDMENTS
 TO THE FLORIDA BUILDING CODE. PLEASE
 AMEND THE PLANS.
  
 4) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWING. A MINIMUM OF 6"
 HIGH NUMBERS IS REQUIRED.
  
 5) WOOD SHOWN ON PLANS. FIRE RATED
 WOOD IS ALLOWED IN THE CITY FIRE LIMTS.
  
 6) PLEASE INDICATE INTERIOR FINISH
 FOR WALLS AND CEILINGS.
  
 7) EFIS NOTED ON CANOPY. ALL
 ARCHITECTURAL TRIM LOCATED IN THE
 FIRE LIMITS SHALL BE NONCOMBUSTIBLE.
  
 8) PLEASE INDICATE ALL WARNING SIGNS
 AND OTHER SAFETY EQUIPMENT PLANNED FOR
 THE FUEL DISPENSING PUMPS.
  
 9) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FUEL TANK INSTALLATIONS.
  
 10) PLEASE INDICATE LOCATIONS OF ALL
 PORTABLE FIRE EXTINGUISHERS.
  
 11) FUEL TANKS TO COMPLY WITH NFPA 30A.
  
 12) STATION TO COMPLY WITH NFPA 30A.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL