| Plan Review Notes For Permit 04050770 |
| Permit Number |
04050770 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-02 00:00:00 | 1) NEED TO SHOW CLASS LOCATIONS ON A | | | SITE PLAN, PER 500.4 OF THE NEC | | | | | | 2) PUMPS NOT SHOWN ON DRAWINGS FOR | | | LOCATION | | | | | | 3) SHOW LOCATION OF EMERGENCY SWITCH | | | | | | 4) RISER SHOWS #12 FEEDING PANEL "B" | | | PANEL "B" HAS A LOAD OF 44 AMPERES? | | | | | | 5) NEED EQUIPMENT SCHEDULE FOR FAST FOOD | | | AREA, THIS LOOKS LIKE A KITCHEN IF SO | | | SHOW GFCI PROTECTION FOR ALL 125V | | | 15,20ACIRCUITS. | | | | | | 6) GAS PUMP PANEL WHICH ONE ON THE | | | RISERIS IT????? | | | | | | 7) CAR WASH IS A WET LOCATION NEED TO | | | NOTE ABOUT 1/4" OF AIR SPACE BETWEEN | | | WALLSAND EQUIPMENT. |
|