| 2004-06-18 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT:04050770 |
| | ADD: 2175 PALM BEACH LAKES BLVD |
| | CONT:FLORIDA GENERAL CONTRACTOR INC |
| | TEL: (561)364-4988 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL |
| | IS NOT DEFINITEY KNOWN, OR IS IN |
| | QUESTIONTHE BUILDING OFFICIAL MAY |
| | REQUIRE EXPLORATIONS, TEST OR OTHER |
| | ADEQUATE PROOF AS TO THE PERMISSIBLE |
| | SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| | TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL |
| | PROPERLY LICENSED IN THE STATE OF |
| | FLORIDA.SHEET A-2 INDICATES REPORT BY |
| | ARDAMEN 3/13/04 |
| | |
| | 3)FBC 13-103.1.2 BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED, THE SUBMITTED |
| | ENERGY CODE COMPLIANCE FORMS SHALL BE |
| | SIGNED BY THE BUILDING OWNER, THE |
| | OWNER'S ARCHETECT OR OTHER AUTHORIZED |
| | AGENT LEGALLY DESIGNATED BY THE OWNER. |
| | |
| | 4) F102.1 WPB AMMENDMENTS, FIRE |
| | DISTRICTSHEET A-1 NO TYPE VI |
| | CONSTRUCTION ALLOW-ED. A) NO EXTERIOR |
| | WALLS CAN BE MADE OF COMBUSTIBLE |
| | MATERIALS,( PLYWOOD SHEATH- ING & WOOD |
| | FRAMING MEMBERS) |
| | |
| | 5) FBC* F102.2.7ARCHITECTURAL TRIM, |
| | ON BUILDINGS LOCATED IN THE FIRE |
| | DISTRICT, SHALL BE CONSTRUCTED OF |
| | APPROVED NON-COMBUSTIBLE MATERIALS OR |
| | FIRE RETARDANT TREATED WOOD.ANNOTATE |
| | THE PLANS TO DEMONSTRATE COMPLIANCE. |
| | SEE A-5/ A-10 PECKY CYPRESS CORBOL |
| | |
| | 6) FBC* F102.2.4ROOF COVERINGS, ON |
| | BUILDINGS LOCATED IN THE FIRE DISTRICT, |
| | SHALL CONFORM TO THE REQUIREMENTS OF |
| | CLASS A OR B ROOF COVERINGS, AS DEFINED |
| | IN FBC 1505.ANNOTATE THE PLANS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 7) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | ON ROOFING DETAILS. PLEASE INDICATE |
| | WHICH DETAIL WILL BE USED AS PER SHEET |
| | A-8A DETAIL #2.(PLYWOOD DECK OR METAL |
| | DECK. ALSO INSULATION ATTATCHMENT) |
| | |
| | 8) 1511.7 ROOF MOUNTED MECHANICAL UNIT |
| | S SHALL BE MOUNTED ON CURBS RAISED A |
| | MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| | FACE, OR WHERE ROOFING MATERIALS EXTEND |
| | BENEATH THE UNIT, ON RAISED EQUIPMENT |
| | SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| | HEIGHT IN ACCORDANCE WITH TABLE 1511.7. |
| | MECH. 301.13 WIND RESISTANCE |
| | MECHANICAL EQUIPMENT, APPLIANCES AND |
| | SUPPORTS THAT ARE EXPOSED TO WIND SHALL |
| | BE DESIGNED AND INSTALLED TO RESIST THE |
| | WIND PRESSURES ON THE EQUIPMENT & THE |
| | SUPPORTS AS DETERMINED IN ACCORDANCE |
| | WITH THE FL BLD CODE. THIS MAY BE |
| | ACCOMPLISHED BY DESIGN OR BY |
| | APPLICATION OF |
| | SECTION 301.13.1. (NO DIMENTIONS SHOWN) |
| | SHEET A-8A CONDENSING UNIT DETAIL. |
| | |
| | 9) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS |
| | B) GLASS BLOCK |
| | C)MULLIONS |
| | D) EXTERIOR DOORS |
| | E) STORM SHUTTERS/IF IMPACT GLAZING IS |
| | NOT USED, |
| | F) ROOF ASSEMBLIES/CEMENT TILE/INSUL |
| | MODIFIED ROOFING/90LB |
| | G) TRUSS ANCHOR |
| | |
| | 10) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATIONPLEASE SEE THE STATE WEBSITE |
| | AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 11)PROVIDE STORM PANEL INFORMATION WITH |
| | INSTALLATION SCHEDULE AND KEY PLAN WITH |
| | SPECIFIC ANCHORS AND MOUNTING TO BE |
| | USEDFOR ALL NON-IMPACT GLAZING. |
| | FBC 1606.1.4. |
| | |
| | 12) FL BLD CODE 2001 SECTION 103.6, |
| | 1606.1.4, 1707.4 & 3401.7.2.4. |
| | PROCEDURES: 1(B) A COMPLETE |
| | INSTALLATIONSCHEDULE SUMMARIZING & |
| | IDENTIFYING |
| | OPENING SIZES, STORY HEIGHTS, UNIT MARK |
| | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM |
| | BAR REINFORCING REQUIREMENTS, WALL |
| | PRES-SURE ZONES, SLAT TYPES, ETC., |
| | SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION |
| | TO FACILITATE PLAN REVIEW AND PERMIT |
| | ISSUANCE. |
| | |
| | 13) 1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | |
| | 14) 1707.4.5.2 MULLIONS SHALL BE |
| | DESIGN-ED TO TRANSFER THE DESIGN |
| | PRESSURE LOADSAPPLIED BY THE WINDOW OR |
| | DOOR ASSEMBLIESTO THE ROUGH OPENING |
| | SUBTRATE. |
| | |
| | 15) A10 DETAIL#2 SHOW MORE DETAILS FOR |
| | CONNECTION TO BAR JOISTS. IF JOISTS ARE |
| | FIVE FEET O.C (5'O.C) PROVIDE DOCUMENTS |
| | OR REPORTS ON SPAN DISTANCE, FOR THE |
| | GAUGE OFTOP TRACKBEING USED AND |
| | HOW IT IS FASTENED TO THE BAR JOISTS. |
| | |
| | 16) SHEET A-6A CANOPY PLAN.PLEASE |
| | SUBMITENGINEERING AND STRUCTUAL |
| | DRAWINGS FOR |
| | CONSTRUCTION OF CANOPY. |
| | |
| | 17) FBC 1606.1.7WIND LOAD.THE PLANS |
| | SHALL STATE THE BASIC WIND SPEED, WIND |
| | IMPORTANCE FACTOR, WIND EXPOSURE |
| | CATEGORY, AND EXTERIOR COMPONENT |
| | AND CLADDING DESIGN WIND PRESSURES.ALSO |
| | PLEASE SPECIFY THE TYPE OF BOLTS AND |
| | ANCHORS TO USED ON COSTRUCTION OF CANOPY |
| | |
| | 18) F102.2.11 EXTERIOR PLASTIC VENEER IS |
| | NOT PERMITTED IN THE FIRE DISTRICT. |
| | PLEASE AMEND PLANS. |
| | |
| | |
| | |
| | NF |